Power size [kW (hp)]
Cable [m (ft)]
Mains voltage [V]
Rise time [
µ
s]
Peak voltage [V]
dU/dt [V/
µ
s]
55–132 (60–150)
30 (98)
690
–
–
–
150 (492)
690
1.03
2045
1590
300 (984)
690
1.41
2132
1217
160–315 (200–350)
30 (98)
690
–
–
–
150 (492)
690
1.00
2022
1617
300 (984)
690
1.15
2097
1459
Table 10.30 IEC dU/dt Test Results for D1h–D8h with Shielded Cables and No Output Filter, 525–690 V
10.13.2 dU/dt Test Results for Enclosures E1h–E4h
Test results for 380–500 V
Power size [kW (hp)]
Cable [m (ft)]
Mains voltage [V]
Rise time [
µ
s]
Peak voltage [V]
dU/dt [V/
µ
s]
315–400 (450–550)
5 (16)
460
0.23
1038
2372
30 (98)
460
0.72
1061
644
150 (492)
460
0.46
1142
1160
300 (984)
460
1.84
1244
283
450–500 (600–650)
5 (16)
460
0.42
1042
1295
30 (98)
460
0.57
1200
820
150 (492)
460
0.63
1110
844
300 (984)
460
2.21
1175
239
Table 10.31 NEMA dU/dt Test Results for E1h–E4h with Unshielded Cables and No Output Filter, 380–500 V
Power size [kW (hp)]
Cable [m (ft)]
Mains voltage [V]
Rise time [
µ
s]
Peak voltage [V]
dU/dt [V/
µ
s]
315–400 (450–550)
5 (16)
460
0.33
1038
2556
30 (98)
460
1.27
1061
668
150 (492)
460
0.84
1142
1094
300 (984)
460
2.25
1244
443
450–500 (600–650)
5 (16)
460
0.53
1042
1569
30 (98)
460
1.22
1200
1436
150 (492)
460
0.90
1110
993
300 (984)
460
2.29
1175
411
Table 10.32 IEC dU/dt Test Results for E1h–E4h with Unshielded Cables and No Output Filter, 380–500 V
Power size [kW (hp)]
Cable [m (ft)]
Mains voltage [V]
Rise time [
µ
s]
Peak voltage [V]
dU/dt [V/
µ
s]
315–400 (450–550)
5 (16)
460
0.17
1017
3176
30 (98)
460
–
–
–
150 (492)
460
0.41
1268
1311
450–500 (600–650)
5 (16)
460
0.17
1042
3126
30 (98)
460
–
–
–
150 (492)
460
0.22
1233
2356
Table 10.33 NEMA dU/dt Test Results for E1h–E4h with Shielded Cables and No Output Filter, 380–500 V
Power size [kW (hp)]
Cable [m (ft)]
Mains voltage [V]
Rise time [
µ
s]
Peak voltage [V]
dU/dt [V/
µ
s]
315–400 (450–550)
5 (16)
460
0.26
1017
3128
30 (98)
460
–
–
–
150 (492)
460
0.70
1268
1448
450–500 (600–650)
5 (16)
460
0.27
1042
3132
30 (98)
460
–
–
–
150 (492)
460
0.52
1233
1897
Table 10.34 IEC dU/dt Test Results for E1h–E4h with Shielded Cables and No Output Filter, 380–500 V