Mains Supply 3 x 380 - 500 V AC
FC 302
P90K
P110
P132
P160
P200
High/ Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft output at
400 V [kW]
90
110
110
132
132
160
160
200
200
250
Typical Shaft output at
460 V [hp]
125
150
150
200
200
250
250
300
300
350
Typical Shaft output at
500 V [kW]
110
132
132
160
160
200
200
250
250
315
Enclosure IP21
D1
D1
D2
D2
D2
Enclosure IP54
D1
D1
D2
D2
D2
Enclosure IP00
D3
D3
D4
D4
D4
Output current
Continuous
(at 400 V) [A]
177
212
212
260
260
315
315
395
395
480
Intermittent (60 s
overload)
(at 400 V) [A]
266
233
318
286
390
347
473
435
593
528
Continuous
(at 460/500 V) [A]
160
190
190
240
240
302
302
361
361
443
Intermittent (60 s
overload)
(at 460/500 V) [A]
240
209
285
264
360
332
453
397
542
487
Continuous kVA
(at 400 V) [kVA]
123
147
147
180
180
218
218
274
274
333
Continuous kVA
(at 460 V) [kVA]
127
151
151
191
191
241
241
288
288
353
Continuous kVA
(at 500 V) [kVA]
139
165
165
208
208
262
262
313
313
384
Max. input current
Continuous
(at 400 V) [A]
171
204
204
251
251
304
304
381
381
463
Continuous
(at 460/500 V) [A]
154
183
183
231
231
291
291
348
348
427
Max. cable size, mains
motor, brake and load
share [mm
2
(AWG
2)
)]
2 x 70
(2 x 2/0)
2 x 70
(2 x 2/0)
2 x 150
(2 x 300 mcm)
2 x 150
(2 x 300 mcm)
2 x 150
(2 x 300 mcm)
Max. external mains fuses
[A]
1
300
350
400
500
630
Estimated power loss
at 400 V [W]
4)
2369
2907
2634
3357
3117
3914
3640
4812
4288
5517
Estimated power loss
at 460 V [W]
2162
2599
2350
3078
2886
3781
3629
4535
3624
5025
Weight,
enclosure IP21, IP54 [kg]
96
104
125
136
151
Weight,
enclosure IP00 [kg]
82
91
112
123
138
Efficiency
4)
0.98
Output frequency
0 - 800 Hz
Heatsink overtemp. trip
90 °C
110 °C
110 °C
110 °C
110 °C
Power card ambient trip
75 °C
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
Table 5.1
General Specifications
VLT
®
Automation Drive FC 300 Operating Instructions
MG33U402 - Rev. 2013-12-16
95