Enclosure
FC 300 power
Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Max trip level
Size
[kW]
Moeller
[A]
A1
0.37-1.5
gG-10
gG-25
PKZM0-16
16
A2
0.37-4.0
gG-10 (0.37-3)
gG-16 (4)
gG-25
PKZM0-25
25
A3
5.5-7.5
gG-16
gG-32
PKZM0-25
25
B3
11-15
gG-40
gG-63
PKZM4-50
50
B4
18.5-30
gG-50 (18.5)
gG-63 (22)
gG-80 (30)
gG-125
NZMB1-A100
100
C3
37-45
gG-100 (37)
gG-160 (45)
gG-150 (37)
gG-160 (45)
NZMB2-A200
150
C4
55-75
aR-200 (55)
aR-250 (75)
aR-250
NZMB2-A250
250
A4
0.37-4
gG-10 (0.37-3)
gG-16 (4)
gG-32
PKZM0-25
25
A5
0.37-7.5
gG-10 (0.37-3)
gG-16 (4-7.5)
gG-32
PKZM0-25
25
B1
11-15
gG-40
gG-80
PKZM4-63
63
B2
18.5-22
gG-50 (18.5)
gG-63 (22)
gG-100
NZMB1-A100
100
C1
30-45
gG-80 (30)
gG-100 (37)
gG-160 (45)
gG-160
NZMB2-A200
160
C2
55-75
aR-200 (55)
aR-250 (75)
aR-250
NZMB2-A250
250
D
90-200
gG-300 (90)
gG-350 (110)
gG-400 (132)
gG-500 (160)
gG-630 (200)
gG-300 (90)
gG-350 (110)
gG-400 (132)
gG-500 (160)
gG-630 (200)
-
-
E
250-400
aR-700 (250)
aR-900 (315-400)
aR-700 (250)
aR-900 (315-400)
-
-
F
450-800
aR-1600 (450-500)
aR-2000 (560-630)
aR-2500 (710-800)
aR-1600 (450-500)
aR-2000 (560-630)
aR-2500 (710-800)
-
-
Table 3.27 380-500 V, Frame Sizes A, B, C, D, E, and F
How to Install
VLT
®
Automation Drive FC 300 Operating Instructions
MG33U402 - Rev. 2013-12-16
59
3
3
Summary of Contents for VLT AutomationDrive FC 302
Page 2: ......