Mains Supply 525-690 V AC
FC 302
P900
P1M0
P1M2
High/ Normal Load*
HO
NO
HO
NO
HO
NO
Typical Shaft output at 550 V [kW]
750
850
850
1000
1000
1100
Typical Shaft output at 575 V [hp]
1050
1150
1150
1350
1350
1550
Typical Shaft output at 690 V [kW]
900
1000
1000
1200
1200
1400
Enclosure IP21, IP54 without/with options
cabinet
F2/ F4
F2/ F4
F2/ F4
Output current
Continuous
(at 550 V) [A]
988
1108
1108
1317
1317
1479
Intermittent (60 s overload)
(at 550 V) [A]
1482
1219
1662
1449
1976
1627
Continuous
(at 575/690 V) [A]
945
1060
1060
1260
1260
1415
Intermittent (60 s overload)
(at 575/690 V) [A]
1418
1166
1590
1386
1890
1557
Continuous KVA
(at 550 V) [KVA]
941
1056
1056
1255
1255
1409
Continuous KVA
(at 575 V) [KVA]
941
1056
1056
1255
1255
1409
Continuous KVA
(at 690 V) [KVA]
1129
1267
1267
1506
1506
1691
Max. input current
Continuous
(at 550 V ) [A]
962
1079
1079
1282
1282
1440
Continuous
(at 575 V) [A]
920
1032
1032
1227
1227
1378
Continuous
(at 690 V) [A]
920
1032
1032
1227
1227
1378
Max. cable size, motor [mm
2
(AWG
2)
)]
12x150
(12x300 mcm)
Max. cable size,mains F2 [mm
2
(AWG
2)
)]
8x240
(8x500 mcm)
Max. cable size,mains F4 [mm
2
(AWG
2)
)]
8x456
(8x900 mcm)
Max. cable size, loadsharing [mm
2
(AWG
2)
)]
4x120
(4x250 mcm)
Max. cable size, brake [mm
2
(AWG
2)
)
6x185
(6x350 mcm)
Max. external mains fuses [A]
1
1600
2000
2500
Estimated power loss, 600V [W]
4)
11329
12909
12570
15358
15258
17602
Estimated power loss, 690V [W]
4)
11681
13305
12997
15865
15763
18173
F3/F4 Max added losses CB or Disconnect
& Contactor
556
665
634
863
861
1044
Max panel options losses
400
Weight,
enclosure IP21, IP54 [kg]
1246/ 1541
1246/ 1541
1280/1575
Weight, Rectifier Module [kg]
136
136
136
Weight, Inverter Module [kg]
102
102
136
Efficiency
4)
0.98
Output frequency
0-500Hz
Heatsink overtemp. trip
105
°
C
105
°
C
95
°
C
Power card ambient trip
75
°
C
* High overload = 160% torque during 60 s., Normal overload = 110% torque during 60 s.
Table 5.9
General Specifications
VLT
®
Automation Drive FC 300 Operating Instructions