1-23 Motor Frequency
Range:
Function:
Size
related
*
[20 -
1000
Hz]
Min - Max motor frequency: 20-1000 Hz.
Select the motor frequency value from the
motor nameplate data. If a value different
from 50 Hz or 60 Hz is selected, adapt the
load independent settings in
1-50 Motor
Magnetisation at Zero Speed
to
1-53 Model
Shift Frequency
. For 87 Hz operation with
230/400 V motors, set the nameplate data
for 230 V/50 Hz. To run at 87 Hz, adapt
4-13 Motor Speed High Limit [RPM]
and
parameter 3-03 Maximum Reference
.
1-24 Motor Current
Range:
Function:
Size
related
*
[ 0.10 -
10000.00 A]
Enter the nominal motor current
value from the motor nameplate
data. This data is used for
calculating motor torque, motor
thermal protection etc.
1-25 Motor Nominal Speed
Range:
Function:
Size related
*
[100 - 60000
RPM]
Enter the nominal motor speed
value from the motor nameplate
data. This data is used for
calculating automatic motor
compensations.
5-12 Terminal 27 Digital Input
Option:
Function:
[2]
*
Coast inverse Functions are described under parameter
group
5-1* Digital Inputs
1-29 Automatic Motor Adaptation (AMA)
Option:
Function:
The AMA function optimises dynamic motor
performance by automatically optimising the
advanced motor parameters (
1-30 Stator
Resistance (Rs)
to
1-35 Main Reactance (Xh)
) at
motor standstill.
Activate the AMA function by pressing [Hand
on] after selecting
[1] Enable complete AMA
or
[2] Enable reduced AMA
. See also
chapter 3.7.1 Final Set-Up and Test
. After a
normal sequence, the display reads: "Press [OK]
to finish AMA". After pressing [OK], the
frequency converter is ready for operation.
This parameter cannot be adjusted while the
motor is running.
[0]
*
OFF
[1]
Enable
complete
AMA
Performs AMA of the stator resistance R
S
, the
rotor resistance R
r
, the stator leakage reactance
1-29 Automatic Motor Adaptation (AMA)
Option:
Function:
X
1
, the rotor leakage reactance X
2
and the main
reactance X
h
.
FC 301:
The complete AMA does not include X
h
measurement for FC 301. Instead, the X
h
value
is determined from the motor database.
1-35 Main Reactance (Xh)
may be adjusted to
obtain optimal start performance.
[2]
Enable
reduced
AMA
Performs a reduced AMA of the stator
resistance R
s
in the system only. Select this
option if an LC filter is used between the
frequency converter and the motor.
Note:
•
For the best adaptation of the frequency
converter, run AMA on a cold motor.
•
AMA cannot be performed while the motor is
running.
•
AMA cannot be performed on permanent magnet
motors.
NOTICE
It is important to set motor parameter group 1-2*
correctly, since these form part of the AMA algorithm.
An AMA must be performed to achieve optimum
dynamic motor performance. It may take up to 10 min,
depending on the power rating of the motor.
NOTICE
Avoid generating external torque during AMA.
NOTICE
If one of the settings in parameter group
1-2* Motor
Data
is changed,
1-30 Stator Resistance (Rs)
to
1-39 Motor
Poles
return to default setting.
3-02 Minimum Reference
Range:
Function:
Size
related
*
[ -999999.999 -
par. 3-03
ReferenceFeed-
backUnit]
Enter the minimum reference. The
minimum reference is the lowest
value obtainable by summing all
references.
Minimum reference is active only
when
3-00 Reference Range
is set to
[0] Min.- Max.
The minimum reference unit
matches:
•
The configuration of
1-00 Configuration Mode
:
How to Programme
VLT
®
Automation Drive FC 300 Operating Instructions
84
MG33U402 - Rev. 2013-12-16
4
4