Mains Supply 525-690 V AC
FC 302
P400
P500
P560
High/ Normal Load*
HO
NO
HO
NO
HO
NO
Typical Shaft output at 550 V [kW]
315
400
400
450
450
500
Typical Shaft output at 575 V [hp]
400
500
500
600
600
650
Typical Shaft output at 690 V [kW]
400
500
500
560
560
630
Enclosure IP21
E1
E1
E1
Enclosure IP54
E1
E1
E1
Enclosure IP00
E2
E2
E2
Output current
Continuous
(at 550 V) [A]
429
523
523
596
596
630
Intermittent (60 sec overload)
(at 550 V) [A]
644
575
785
656
894
693
Continuous
(at 575/690 V) [A]
410
500
500
570
570
630
Intermittent (60 s overload)
(at 575/690 V) [A]
615
550
750
627
855
693
Continuous KVA
(at 550 V) [KVA]
409
498
498
568
568
600
Continuous KVA
(at 575 V) [KVA]
408
498
498
568
568
627
Continuous KVA
(at 690 V) [KVA]
490
598
598
681
681
753
Max. input current
Continuous
(at 550 V ) [A]
413
504
504
574
574
607
Continuous
(at 575 V) [A]
395
482
482
549
549
607
Continuous
(at 690 V) [A]
395
482
482
549
549
607
Max. cable size, mains, motor and
load share [mm
2
(AWG)]
4x240 (4x500 mcm)
4x240 (4x500 mcm)
4x240 (4x500 mcm)
Max. cable size, brake [mm
2
(AWG)]
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
Max. external mains fuses [A]
1
700
900
900
Estimated power loss
at 600 V [W]
4)
4478
5623
6153
7018
7007
7793
Estimated power loss
at 690 V [W]
4)
4605
5794
6328
7221
7201
8017
Weight,
enclosure IP21, IP54 [kg]
263
272
313
Weight,
enclosure IP00 [kg]
221
236
277
Efficiency
4)
0.98
Output frequency
0 - 500Hz
Heatsink overtemp. trip
110
°
C
Power card ambient trip
75
°
C
* High overload = 160% torque during 60 s., Normal overload = 110% torque during 60 s.
Table 5.7
General Specifications
VLT
®
Automation Drive FC 300 Operating Instructions
MG33U402 - Rev. 2013-12-16
101
5
5