No. Description
Warning
Alarm/Trip
Alarm/Trip Lock
Parameter
Reference
57
AMA time-out
X
58
AMA internal fault
X
X
59
Current limit
X
60
External Interlock
X
X
61
Feedback Error
(X)
(X)
4-30 Motor Feedback
Loss Function
62
Output Frequency at Maximum Limit
X
63
Mechanical Brake Low
(X)
2-20 Release Brake
Current
64
Voltage Limit
X
65
Control Board Over-temperature
X
X
X
66
Heat sink Temperature Low
X
67
Option Configuration has Changed
X
68
Safe Stop
(X)
(X)
1)
5-19 Terminal 37 Safe
Stop
69
Pwr. Card Temp
X
X
70
Illegal FC configuration
X
71
PTC 1 Safe Stop
72
Dangerous failure
73
Safe Stop Auto Restart
(X)
(X)
5-19 Terminal 37 Safe
Stop
74
PTC Thermistor
X
75
Illegal Profile Sel.
X
76
Power Unit Setup
X
77
Reduced power mode
X
14-59 Actual Number of
Inverter Units
78
Tracking Error
(X)
(X)
4-34 Tracking Error
Function
79
Illegal PS config
X
X
80
Drive Initialized to Default Value
X
81
CSIV corrupt
X
82
CSIV parameter error
X
83
Illegal Option Combination
X
84
No Safety Option
X
88
Option Detection
X
89
Mechanical Brake Sliding
X
90
Feedback Monitor
(X)
(X)
17-61 Feedback Signal
Monitoring
91
Analog input 54 wrong settings
X
S202
163
ATEX ETR cur.lim.warning
X
164
ATEX ETR cur.lim.alarm
X
165
ATEX ETR freq.lim.warning
X
166
ATEX ETR freq.lim.alarm
X
250
New spare parts
X
251
New Type Code
X
X
Table 6.1 Alarm/Warning Code List
(X) Dependent on parameter
1) Can not be Auto reset via 14-20 Reset Mode
A trip is the action when an alarm has appeared. The trip
coasts the motor and can be reset by pressing [Reset] or
make a reset by a digital input (parameter group
5-1*
Digital Inputs
[1]). The origin event that caused an alarm
cannot damage the frequency converter or cause
dangerous conditions. A trip lock is an action when an
alarm occurs, which may damage the frequency converter
Warnings and Alarms
VLT
®
Automation Drive FC 300 Operating Instructions
MG33U402 - Rev. 2013-12-16
107
6
6
Summary of Contents for VLT AutomationDrive FC 302
Page 2: ......