![background image](http://html1.mh-extra.com/html/danfoss/vlt-automationdrive-fc-301/vlt-automationdrive-fc-301_instruction-manual_3430507063.webp)
8.1.4 Line Power Supply 525–690 V (FC 302 only)
Type designation
P1K1
P1K5
P2K2
P3K0
P4K0
P5K5
P7K5
High/Normal overload
1)
HO/NO
HO/NO
HO/NO
HO/NO
HO/NO
HO/NO
HO/NO
Typical shaft output (hp [kW])
1.5 [1.1]
2 [1.5]
3 [2.2]
4 [3.0]
5 [4.0]
7.5 [5.5]
10 [7.5]
Enclosure protection rating IP20
A3
A3
A3
A3
A3
A3
A3
Output current
Continuous (525–550 V) [A]
2.1
2.7
3.9
4.9
6.1
9.0
11.0
Intermittent (525–550 V) [A]
3.4
4.3
6.2
7.8
9.8
14.4
17.6
Continuous (551–690 V) [A]
1.6
2.2
3.2
4.5
5.5
7.5
10.0
Intermittent (551–690 V) [A]
2.6
3.5
5.1
7.2
8.8
12.0
16.0
Continuous KVA 525 V
1.9
2.5
3.5
4.5
5.5
8.2
10.0
Continuous KVA 690 V
1.9
2.6
3.8
5.4
6.6
9.0
12.0
Maximum input current
Continuous (525–550 V) [A]
1.9
2.4
3.5
4.4
5.5
8.1
9.9
Intermittent (525–550 V) [A]
3.0
3.9
5.6
7.0
8.8
12.9
15.8
Continuous (551–690 V) [A]
1.4
2.0
2.9
4.0
4.9
6.7
9.0
Intermittent (551–690 V) [A]
2.3
3.2
4.6
6.5
7.9
10.8
14.4
Additional specifications
Maximum cable cross-section
2)
for line power, motor,
brake and load sharing [mm
2
] ([AWG])
4, 4, 4 (12, 12, 12) (min. 0.2 (24)
Maximum cable cross-section
2)
for disconnect
[mm
2
] ([AWG])
6, 4, 4 (10, 12, 12)
Estimated power loss at rated maximum load (hp
[W])
3)
0.059 [44] 0.081 [60] 0.118 [88]
0.161
[120]
0.215
[160]
0.295
[220]
0.402
[300]
Efficiency
4)
0.96
0.96
0.96
0.96
0.96
0.96
0.96
Table 8.10 A3 Enclosure, Line Power Supply 525–690 V IP20/Protected Chassis, P1K1-P7K5
Specifications
Instruction Manual
MG33AP22
Danfoss A/S © Rev. 09/2014 All rights reserved.
61
8
8