6.
Press [OK] to accept the change.
7.
Press either [Back] twice to enter Status, or press
[Main Menu] once to enter the Main Menu.
View changes
Quick Menu Q5 - Changes Made
lists all parameters
changed from default settings.
•
The list only shows parameters, which have been
changed in the current edit set-up.
•
Parameters, which have been reset to default
values, are not listed.
•
The message
Empty
indicates that no parameters
have been changed.
5.3.6 Restoring Default Settings
NOTICE!
Risk of losing programming, motor data, localization,
and monitoring records by restoration of default
settings. To provide a backup, upload data to the LCP
before initialization.
Restoring the default parameter settings is done by initiali-
zation of the adjustable frequency drive. Initialization is
carried out through
14-22 Operation Mode
(recommended)
or manually.
•
Initialization using
14-22 Operation Mode
does not
reset adjustable frequency drive settings, such as
operating hours, serial communication selections,
personal menu settings, fault log, alarm log, and
other monitoring functions.
•
Manual initialization erases all motor,
programming, localization, and monitoring data
and restores factory default settings.
Recommended initialization procedure, via
14-22 Operation Mode
1.
Press [Main Menu] twice to access parameters.
2.
Scroll to
14-22 Operation Mode
and press [OK].
3.
Scroll to
[2] Initialization
and press [OK].
4.
Remove power to the unit and wait for the
display to turn off.
5.
Apply power to the unit.
Default parameter settings are restored during start-up.
This may take slightly longer than normal.
6.
Alarm 80 is displayed.
7.
Press [Reset] to return to operation mode.
Manual initialization procedure
1.
Remove power to the unit and wait for the
display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at
the same time while applying power to the unit
(approximately 5 s or until audible click and fan
starts).
Factory default parameter settings are restored during
start-up. This may take slightly longer than normal.
Manual initialization does not reset the following
adjustable frequency drive information:
•
15-00 Operating hours
•
15-03 Power-ups
•
15-04 Over Temps
•
15-05 Over Volts
5.4 Basic Programming
5.4.1 Commissioning with SmartStart
The SmartStart wizard enables fast configuration of basic
motor and application parameters.
•
SmartStart starts automatically, at first power-up
or after initialization of the adjustable frequency
drive.
•
Follow the on-screen instructions to complete the
commissioning of the adjustable frequency drive.
Always reactivate SmartStart by selecting
Quick
Menu Q4 - SmartStart
.
•
For commissioning without use of the SmartStart
wizard, refer to
chapter 5.4.2 Commissioning via
or the
Programming Guide
.
NOTICE!
Motor data is required for the SmartStart set-up. The
required data is normally available on the motor
nameplate.
Commissioning
Instruction Manual
26