3.8. Final Set-Up and Test
3.8.1. Final Set-Up and Test
To test the set-up and ensure that the frequency converter is running, follow these steps.
Step 1. Locate the motor name plate
NB!
The motor is either star- (Y) or delta- connected (
Δ
). This information is located on
the motor name plate data.
Step 2. Enter the motor name plate da-
ta in this parameter list.
To access this list first press the [QUICK
MENU] key then select “Q2 Quick Setup”.
1. Motor Power [kW]
or Motor Power [HP]
par. 1-20
par. 1-21
2. Motor Voltage
par. 1-22
3. Motor Frequency
par. 1-23
4. Motor Current
par. 1-24
5. Motor Nominal Speed
par. 1-25
Step 3. Activate the Automatic Motor
Adaptation (AMA)
Performing an AMA will ensure optimum performance. The AMA measures the values
from the motor model equivalent diagram.
1.
Connect terminal 37 to terminal 12 (if terminal 37 is available).
2.
Connect terminal 27 to terminal 12 or set par. 5-12 to 'No function' (par. 5-12 [0])
3.
Activate the AMA par. 1-29.
4.
Choose between complete or reduced AMA. If a Sine-wave filter is mounted, run only
the reduced AMA, or remove the Sine-wave filter during the AMA procedure.
5.
Press the [OK] key. The display shows “Press [Hand on] to start”.
VLT
®
Automation Drive FC 300
Operating Instructions High Power