Surroundings:
Enclosure
IP 21/ Type 1, IP 54/ Type 12
Vibration test
1.0 g
Max. relative humidity
5% - 95%(IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43
class H
2
5
Ambient temperature
1)
Max. 50 °C (24-hour average maximum 45 °C)
1) For high ambient temperature, see special conditions in the Design Guide
Minimum ambient temperature during full-scale operation
0 °C
Minimum ambient temperature at reduced performance
- 10 °C
Temperature during storage/transport
-25 - +65/70 °C
Maximum altitude above sea level without derating
1000 m
Derating for high altitude, see special conditions in the Design Guide
EMC standards, Emission
EN 61800-3, EN 61000-6-3/4, EN 55011
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN
61000-4-6
See section on special conditions in the Design Guide
Protection and Features:
•
Electronic thermal motor protection against overload.
•
Temperature monitoring of the heatsink ensures that the frequency converter trips if the
temperature reaches a predefined level. An overload temperature cannot be reset until
the temperature of the heatsink is below the values stated in the tables on the following
pages (Guideline - these temperatures may vary for different power sizes, enclosures
etc.).
•
The frequency converter is protected against short-circuits on motor terminals U, V, W.
•
If a mains phase is missing, the frequency converter trips or issues a warning (depending
on the load).
•
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips
if the intermediate circuit voltage is too low or too high.
•
The frequency converter constantly checks for critical levels of internal temperature, load
current, high voltage on the intermediate circuit and low motor speeds. As a response
to a critical level, the frequency converter can adjust the switching frequency and/ or
change the switching pattern in order to ensure the performance of the drive.
VLT
®
Automation Drive FC 300
Operating Instructions High Power
5. General Specifications
MG.33.U1.02 - VLT
®
is a registered Danfoss trademark
111