2) Except safe stop input Terminal 37.
3) Terminal 37 can only be used as safe stop input. Terminal 37 is suitable for category 3 in-
stallations according to EN 954-1 (safe stop according to category 0 EN 60204-1) as required by
the EU Machinery Directive 98/37/EC. Terminal 37 and the Safe Stop function are designed in
conformance with EN 60204-1, EN 50178, EN 61800-2, EN 61800-3, and EN 954-1. For correct
and safe use of the Safe Stop function follow the related information and instructions in the
Design Guide.
Analog inputs:
Number of analog inputs
2
Terminal number
53, 54
Modes
Voltage or current
Mode select
Switch S201 and switch S202
Voltage mode
Switch S201/switch S202 = OFF (U)
Voltage level
-10 to +10 V (scaleable)
Input resistance, R
i
approx. 10 k
Ω
Max. voltage
± 20 V
Current mode
Switch S201/switch S202 = ON (I)
Current level
0/4 to 20 mA (scaleable)
Input resistance, R
i
approx. 200
Ω
Max. current
30 mA
Resolution for analog inputs
10 bit (+ sign)
Accuracy of analog inputs
Max. error 0.5% of full scale
Bandwidth
100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage
terminals.
Pulse/encoder inputs:
Programmable pulse/encoder inputs
2/1
Terminal number pulse/encoder
29
1)
, 33
2)
/ 32
3)
, 33
3)
Max. frequency at terminal 29, 32, 33
110 kHz (Push-pull driven)
Max. frequency at terminal 29, 32, 33
5 kHz (open collector)
Min. frequency at terminal 29, 32, 33
4 Hz
Voltage level
see section on Digital input
Maximum voltage on input
28 V DC
Input resistance, R
i
approx. 4 k
Ω
Pulse input accuracy (0.1 - 1 kHz)
Max. error: 0.1% of full scale
Encoder input accuracy (1 - 110 kHz)
Max. error: 0.05 % of full scale
The pulse and encoder inputs (terminals 29, 32, 33) are galvanically isolated from the supply
voltage (PELV) and other high-voltage terminals.
1) FC 302 only
2) Pulse inputs are 29 and 33
5. General Specifications
VLT
®
Automation Drive FC 300
Operating Instructions High Power
108
MG.33.U1.02 - VLT
®
is a registered Danfoss trademark
5