Line Power Supply 3 x 380–480 V AC
P500
P560
P630
P710
Typical Shaft output at 400
V [kW]
500
560
630
710
Typical Shaft output at 460
V [HP]
650
750
900
1000
Enclosure IP21, 54
F17
F17
F17
F17
Output current
Continuous
(at 400 V) [A]
880
990
1120
1260
Intermittent (60 sec over-
load)
(at 400 V) [A]
968
1089
1232
1386
Continuous
(at 460/ 480 V) [A]
780
890
1050
1160
Intermittent (60 sec over-
load)
(at 460/480 V) [A]
858
979
1155
1276
Continuous KVA
(at 400 V) [KVA]
610
686
776
873
Continuous KVA
(at 460 V) [KVA]
621
709
837
924
Max. input current
Continuous
(at 400 V) [A]
857
964
1090
1227
Continuous (at 460/480 V)
[A]
759
867
1022
1129
Max. cable size,motor
[mm
2
(AWG
2)
)]
8x150
(8x300 mcm)
Max. cable size, line power
F1/F2 [mm
2
(AWG
2)
)]
8x240
(8x500 mcm)
Max. cable size, line power
F3/F4 [mm
2
(AWG
2)
)]
8x456
(8x900 mcm)
Max. cable size, load shar-
ing [mm2 (AWG
2)
)]
4x120
(4x250 mcm)
Max. cable size, brake
[mm
2
(AWG
2)
)
4x185
(4x350 mcm)
Max. external pre-fuses [A]
1
1600
2000
Est. motor power loss at
rated max. load [W]
4)
, 400
V, F1 & F2
10647
12338
13201
15436
Est. motor power loss at
rated max. load [W]
4)
, 460
V, F1 & F2
9414
11006
12353
14041
Max. added losses of A1
RFI, Circuit Breaker or Dis-
connect, & Contactor, F3 &
F4
963
1054
1093
1230
Max Panel Options Losses
400
Weight,
enclosure IP21, IP 54 [kg]
2009
Weight Drive
section [kg]
1004
Weight Filter
section [kg]
1005
Efficiency
4)
0.96
Output frequency
0–600 Hz
Heatsink overtemp. trip
203°F [95
°
C]
Power card ambient trip
154.4°F [68
°
C]
1) For type of fuse, see the section Fuses.
2) American Wire Gauge.
3) Measured using 16.4 ft [5 m] shielded motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be /-15% (tolerance relates to variety in voltage and cable
conditions). Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss
in the adjustable frequency drive and opposite. If the switching frequency is increased compared to the default setting, the power losses may
rise significantly.LCP and typical control card power consumptions are included. Further options and customer load may add up to 30 W to the
losses. (Though typical, only 4 W extra for a fully loaded control card, or options for slot A or slot B, each.)
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/-5%).
VLT AQUA Low Harmonic Drive Instruction
Manual
8 General Specifications
MG.20.T1.22 - VLT
®
is a registered Danfoss trademark
8-7