[143]
Ext. CL 1 4-20 mA
0 - 100%
[144]
Ext. CL 2 4-20 mA
0 - 100%
[145]
Ext. CL 3 4-20 mA
0 - 100%
NOTE!
Values for setting the minimum reference are found in open-loop par. 3-02
and for closed-loop par. 20-13
Minimum Reference/
Feedb.
- values for maximum reference for open-loop are found in par. 3-03
and for closed-loop par. 20-14
Maximum Reference/
Feedb.
.
6-51 Terminal 42 Output Min Scale
Range:
Function:
0.00 %*
[0.00 - 200.00 %]
6-52 Terminal 42 Output Max Scale
Range:
Function:
100.00 %* [0.00 - 200.00 %]
EXAMPLE 1:
Variable value= OUTPUT FREQUENCY, range = 0–100 Hz
Range needed for output = 0–50 Hz
Output signal 0 or 4 mA is needed at 0 Hz (0% of range) - set par. 6-51
to 0%
Output signal 20 mA is needed at 50 Hz (50% of range) - set par. 6-52
to 50%
EXAMPLE 2:
Variable= FEEDBACK, range= -200% to +200%
Range needed for output= 0–100%
Output signal 0 or 4 mA is needed at 0% (50% of range) - set par. 6-51
to 50%
Output signal 20 mA is needed at 100% (75% of range) - set par. 6-52
6 How to Program the Low Harmonic Drive
VLT AQUA Low Harmonic Drive Instruction
Manual
6-30
MG.20.T1.22 - VLT
®
is a registered Danfoss trademark
6