6.4.12 14-** Special Functions
Par.
No. #
Parameter description
Default value
(SR = Size related)
4 set-up
Change dur-
ing operation
Conver-
sion index
Type
14-0* Inverter Switching
14-00 Switching Pattern
null
All set-ups
TRUE
-
Uint8
14-01 Switching Frequency
null
All set-ups
TRUE
-
Uint8
14-03 Overmodulation
[1] On
All set-ups
FALSE
-
Uint8
14-04 PWM Random
[0] Off
All set-ups
TRUE
-
Uint8
14-1* Mains On/Off
14-10 Mains Failure
[0] No function
All set-ups
FALSE
-
Uint8
14-11 Mains Voltage at Mains Fault
ExpressionLimit
All set-ups
TRUE
0
Uint16
14-12 Function at Mains Imbalance
[0] Trip
All set-ups
TRUE
-
Uint8
14-2* Reset Functions
14-20 Reset Mode
null
All set-ups
TRUE
-
Uint8
14-21 Automatic Restart Time
10 s
All set-ups
TRUE
0
Uint16
14-22 Operation Mode
[0] Normal operation
All set-ups
TRUE
-
Uint8
14-23 Typecode Setting
null
2 set-ups
FALSE
-
Uint8
14-25 Trip Delay at Torque Limit
60 s
All set-ups
TRUE
0
Uint8
14-26 Trip Delay at Inverter Fault
ExpressionLimit
All set-ups
TRUE
0
Uint8
14-28 Production Settings
[0] No action
All set-ups
TRUE
-
Uint8
14-29 Service Code
0 N/A
All set-ups
TRUE
0
Int32
14-3* Current Limit Ctrl.
14-30 Current Lim Cont, Proportional Gain
100 %
All set-ups
FALSE
0
Uint16
14-31 Current Lim Contr, Integration Time
0.020 s
All set-ups
FALSE
-3
Uint16
14-32 Current Lim Ctrl, Filter Time
26.0 ms
All set-ups
TRUE
-4
Uint16
14-4* Energy Optimizing
14-40 VT Level
66 %
All set-ups
FALSE
0
Uint8
14-41 AEO Minimum Magnetization
ExpressionLimit
All set-ups
TRUE
0
Uint8
14-42 Minimum AEO Frequency
10 Hz
All set-ups
TRUE
0
Uint8
14-43 Motor Cos-Phi
ExpressionLimit
All set-ups
TRUE
-2
Uint16
14-5* Environment
14-50 RFI 1
[1] On
1 set-up
FALSE
-
Uint8
14-51 DC Link Compensation
[1] On
1 set-up
TRUE
-
Uint8
14-52 Fan Control
[0] Auto
All set-ups
TRUE
-
Uint8
14-53 Fan Monitor
[1] Warning
All set-ups
TRUE
-
Uint8
14-55 Output Filter
[0] No Filter
1 set-up
FALSE
-
Uint8
14-59 Actual Number of Inverter Units
ExpressionLimit
1 set-up
FALSE
0
Uint8
14-6* Auto Derate
14-60 Function at Overtemperature
[0] Trip
All set-ups
TRUE
-
Uint8
14-61 Function at Inverter Overload
[0] Trip
All set-ups
TRUE
-
Uint8
14-62 Inv. Overload Derate Current
95 %
All set-ups
TRUE
0
Uint16
VLT AQUA Low Harmonic Drive Instruction
Manual
6 How to Program the Low Harmonic Drive
MG.20.T1.22 - VLT
®
is a registered Danfoss trademark
6-57