8.4 Fuses and Circuit Breakers
To protect the drive system in case 1 or more internal components break down within a drive module, use fuses and/or
circuit breakers at the mains supply side.
8.4.1.1 Branch Circuit Protection
To protect the installation against electrical and fire hazards, protect all branch circuits in an installation against short circuit
and overcurrent according to national and international regulations.
8.4.1.2 Short-circuit Protection
Danfoss recommends the fuses listed in
chapter 8.4.1.3 Recommended Fuses for CE Compliance
and
chapter 8.4.1.4 Recommended Fuses for UL Compliance
to achieve CE or UL Compliance in the protection of service personnel
and property against the consequences of component breakdown in the drive modules.
8.4.1.3 Recommended Fuses for CE Compliance
Number of drive
modules
FC 302
FC 102/
FC 202
Recommended fuse
(maximum)
2
N450
N500
aR-1600
4
N500
N560
aR-2000
4
N560
N630
aR-2000
4
N630
N710
aR-2500
4
N710
N800
aR-2500
4
N800
N1M0
aR-2500
Table 8.3 6-Pulse Drive Systems (380–500 V AC)
Number of drive
modules
FC 302
FC 102/
FC 202
Recommended fuse
(maximum)
2
N250
N315
aR-630
2
N315
N355
aR-630
2
N355
N400
aR-630
2
N400
N450
aR-800
2
N450
N500
aR-800
4
N500
N560
aR-900
4
N560
N630
aR-900
4
N630
N710
aR-1600
4
N710
N800
aR-1600
4
N800
N1M0
aR-1600
Table 8.4 12-Pulse Drive Systems (380–500 V AC)
Number of drive
modules
FC 302
FC 102/
FC 202
Recommended fuse
(maximum)
4
N630
N710
aR-1600
4
N710
N800
aR-2000
4
N800
N900
aR-2500
4
N900
N1M0
aR-2500
4
N1M0
N1M2
aR-2500
Table 8.5 6-Pulse Drive Systems (525–690 V AC)
Number of drive
modules
FC 302
FC 102/
FC 202
Recommended fuse
(maximum)
2
N250
N315
aR-550
2
N315
N355
aR-630
2
N355
N400
aR-630
2
N400
N500
aR-630
2
N500
N560
aR-630
2
N560
N630
aR-900
4
N630
N710
aR-900
4
N710
N800
aR-900
4
N800
N900
aR-900
4
N900
N1M0
aR-1600
4
N1M0
N1M2
aR-1600
Table 8.6 12-Pulse Drive Systems (525–690 V AC)
Considerations During Insta...
Design Guide
MG37N102
Danfoss A/S © 6/2016 All rights reserved.
87
8
8
Summary of Contents for VLT 380-500 V
Page 2: ......