![Danfoss VLT 380-500 V Design Manual Download Page 53](http://html1.mh-extra.com/html/danfoss/vlt-380-500-v/vlt-380-500-v_design-manual_3871573053.webp)
Power range
N500
N560
Drive modules
2
2
Rectifier configuration
12-pulse
High/normal load
HO
NO
HO
NO
Typical shaft output at 525–550 V [kW]
400
450
450
500
Typical shaft output at 575 V [hp]
500
600
600
650
Typical shaft output at 690 V [kW]
500
560
560
630
Protection rating
IP00
Efficiency
0.98
Output frequency [Hz]
0–590
Heat sink overtemperature trip [°C (°F)]
110 (230)
Power card ambient trip [°C (°F)]
80 (176)
Output current [A]
Continuous (at 550 V)
523
596
596
630
Intermittent (60 s overload) at 550 V
785
656
894
693
Continuous (at 575/690 V)
500
570
570
630
Intermittent (60 s overload) at 575/690 V
750
627
627
693
Continuous (at 550 V) [kVA]
498
568
568
600
Continuous (at 575 V) [kVA]
498
568
568
627
Continuous (at 690 V) [kVA]
598
681
681
753
Input current [A]
Continuous (at 550 V)
504
574
574
607
Continuous (at 575 V)
482
549
549
607
Continuous (at 690 V)
482
549
549
607
Power losses [W]
Drive modules at 600 V
6016
6995
6941
7431
Drive modules at 690 V
5886
6831
6766
7638
AC busbars at 575 V
546
550
550
553
DC busbars during regeneration
186
186
191
191
Maximum cable size [mm
2
(mcm)]
Mains
1)
4x120 (250)
Motor
4x120 (250)
Brake
4x95 (3/0)
Regeneration terminals
4x120 (250)
Maximum external mains fuses
700 V, 630 A
Table 6.14 FC 302, 525–690 V AC Mains Supply (2-Drive System)
1) For 12-pulse units, the cables between the star and delta terminals must be equal in number and length.
Specifications
Design Guide
MG37N102
Danfoss A/S © 6/2016 All rights reserved.
51
6
6
Summary of Contents for VLT 380-500 V
Page 2: ......