7.3.2 Digital Inputs - Terminal X30/1-4
Digital Input
Number of digital inputs
4 (6)
Terminal number
18, 19, 27, 29, 32, 33
Logic
PNP or NPN
Voltage level
0–24 V DC
Voltage level, logic 0 PNP (GND=0 V)
<5 V DC
Voltage level, logic 1 PNP (GND=0 V)
>10 V DC
Voltage level, logic 0 NPN (GND=24 V)
<14 V DC
Voltage level, logic 1 NPN (GND=24 V)
>19 V DC
Maximum voltage on input
28 V continuous
Pulse frequency range
0–110 kHz
Duty cycle, minimum pulse width
4.5 ms
Input impedance
>2 kΩ
7.3.3 Analog Inputs - Terminal X30/11, 12
Analog Input
Number of analog inputs
2
Terminal number
53, 54, X30.11, X30.12
Modes
Voltage
Voltage level
-10 V to +10 V
Input impedance
>10 k
Ω
Maximum voltage
20 V
Resolution for analog inputs
10 bit (+ sign)
Accuracy of analog inputs
Maximum error 0.5% of full scale
Bandwidth
VLT
®
AutomationDrive FC 302: 100 Hz
7.3.4 Digital Outputs - Terminal X30/6, 7
Digital Output
Number of digital outputs
2
Terminal number
X30.6, X30.7
Voltage level at digital/frequency output
0–24 V
Maximum output current
40 mA
Maximum load
≥
600
Ω
Maximum capacitive load
<10 nF
Minimum output frequency
0 Hz
Maximum output frequency
≤
32 kHz
Accuracy of frequency output
Maximum error: 0.1% of full scale
7.3.5 Analog Output - Terminal X30/8
Analog Output
Number of analog outputs
1
Terminal number
42
Current range at analog output
0–20 mA
Maximum load GND - analog output
500
Ω
Accuracy on analog output
Maximum error: 0.5% of full scale
Resolution on analog output
12 bit