Power range
N710
N800
N900
N1M0
N1M2
Drive modules
4
4
4
4
Rectifier configuration
6-pulse/12-pulse
High/normal load
NO
NO
NO
NO
NO
Typical shaft output at 525–550 V [kW]
560
670
750
850
1000
Typical shaft output at 575 V [hp]
750
950
1050
1150
1350
Typical shaft output at 690 V [kW]
710
800
900
1000
1200
Protection rating
IP00
Efficiency
0.98
Output frequency [Hz]
0–590
Heat sink overtemperature trip [°C (°F)]
110 (230)
Power card ambient trip [°C (°F)]
80 (176)
Output current [A]
Continuous (at 550 V)
763
889
988
1108
1317
Intermittent (60 s overload) at 550 V
839
978
1087
1219
1449
Continuous (at 575/690 V)
730
850
945
1060
1260
Intermittent (60 s overload) at 575/690 V
803
935
1040
1166
1590
Continuous (at 550 V)
727
847
941
1056
1056
Continuous (at 575 V)
727
847
941
1056
1056
Continuous (at 690 V)
872
1016
1129
1267
1506
Input current [A]
Continuous (at 550 V)
743
866
962
1079
1282
Continuous (at 575 V)
711
828
920
1032
1227
Continuous (at 690 V)
711
828
920
1032
1227
Power losses [W]
Drive modules at 575 V
8683
10166
11406
12852
15762
Drive modules at 690 V
8559
9996
11188
12580
15358
AC busbars at 575 V
644
653
661
672
695
DC busbars during regeneration
198
208
218
231
256
Maximum cable size [mm
2
(mcm)]
Mains
1)
4x120 (250)
6x120 (250)
8x120 (250)
Motor
4x120 (250)
6x120 (250)
8x120 (250)
Brake
8x70 (2/0)
8x95 (3/0)
Regeneration terminals
4x150 (300)
6x120 (250)
6x150 (300)
8x120 (250)
Maximum external mains fuses
6-pulse configuration
700 V, 1600 A
700 V, 2000 A
12-pulse configuration
700 V, 900 A
700 V, 1500 A
Table 6.5 FC 102, 525–690 V AC Mains Supply (4-Drive System)
1) For 12-pulse units, the cables between the star and delta terminals must be equal in number and length.
Specifications
VLT
®
Parallel Drive Modules
42
Danfoss A/S © 6/2016 All rights reserved.
MG37N102
6
6