![Danfoss VLT 380-500 V Design Manual Download Page 55](http://html1.mh-extra.com/html/danfoss/vlt-380-500-v/vlt-380-500-v_design-manual_3871573055.webp)
6.6 Mains Supply to Drive Module
Mains supply
1)
Supply terminals
R/91, S/92, T/93
Supply voltage
2)
380–480, 500 V 690 V
±
10%10%, 525–690 V
±
10%
Supply frequency
50/60 Hz
±
5%
Maximum temporary imbalance between mains phases
3.0% of rated supply voltage
True power factor (
λ
)
≥
0.98 nominal at rated load
Displacement power factor (cos
Φ
)
(Approximately 1)
Switching on input supply L1, L2, L3
Maximum 1 time per 2 minutes
Environment according to EN 60664-1
Overvoltage category III/pollution degree 2
1) The unit is suitable for use on a circuit capable of delivering not more than 85000 RMS symmetrical Amperes, 480/600 V.
2) Mains voltage low/mains voltage drop-out:
During low mains voltage, the drive module continues until the DC-link voltage drops below the minimum stop level, which
corresponds typically to 15% below the lowest rated supply voltage. Power-up and full torque cannot be expected at mains
voltage lower than 10% below the lowest rated supply voltage. The drive module trips for a detected mains drop-out.
6.7 Motor Output and Motor Data
Motor output
Motor terminals
U/96, V/97, W/98
Output voltage
0–100% of supply voltage
Output frequency
0–590 Hz
Switching on output
Unlimited
Ramp times
1–3600 s
Torque characteristics
Overload torque (constant torque)
Maximum 150% for 60 s
1)
Starting torque
Maximum 180% up to 0.5 s
1)
Overload torque (variable torque)
Maximum 110% for s
1)
Starting torque (variable torque)
Maximum 135% for s
1) Percentage relates to the nominal torque.
Efficiency
Efficiency
98%
1)
1) Efficiency measured at nominal current. For energy efficiency class, see chapter 6.9 Ambient Conditions for Drive Modules. For
part load losses, see www.danfoss.com/vltenergyefficiency.
6.8 12-Pulse Transformer Specifications
Connection
Dy11 d0 or Dyn 11d0
Phase shift between secondaries
30
°
Voltage difference between secondaries
<0.5%
Short-circuit impedance of secondaries
>5%
Short-circuit impedance difference between secondaries
<5% of short-circuit impedance
Other
No grounding of the secondaries allowed. Static shield recommended
6.9 Ambient Conditions for Drive Modules
Environment
IP rating
IP00
Acoustic noise
84 dB (running at full load)
Vibration test
1.0 g
Vibration and shock (IEC 60721-33-3)
Class 3M3
Maximum relative humidity
5–95% (IEC 721–3–3; Class 3K3 (non-condensing)) during operation
Specifications
Design Guide
MG37N102
Danfoss A/S © 6/2016 All rights reserved.
53
6
6
Summary of Contents for VLT 380-500 V
Page 2: ......