Terminal
Parameter
Default
setting
Description
Digital inputs/outputs
12, 13
–
+24 V DC
Digital inputs. 24 V DC supply
voltage. Maximum output current
is 200 mA total for all 24 V loads.
Usable for digital inputs and
external transducers.
18
Parameter 5-10 Terminal 18 Digital Input
[8] Start
19
Parameter 5-11 Terminal 19 Digital Input
[10] Reversing
32
Parameter 5-14 Terminal 32 Digital Input
[0] No operation
33
Parameter 5-15 Terminal 33 Digital Input
[0] No operation
27
Parameter 5-12 Terminal 27 Digital Input
[2] Coast inverse
Selectable for digital input and
output. Default setting is input.
29
Parameter 5-13 Terminal 29 Digital Input
[14] Jog
20
–
–
Common for digital inputs and 0 V
potential for 24 V supply.
37
–
Safe Torque Off (STO)
Safe input (optional). Used for STO.
Analog inputs/outputs
39
–
–
Common for analog output.
42
Parameter 6-50 Terminal 42 Output
Speed 0 – high limit
Programmable analog output. The
analog signal is 0–20 mA or 4–
20 mA at a maximum of 500
Ω
10 V DC analog supply voltage.
15 mA maximum commonly used
for potentiometer or thermistor.
50
–
+10 V DC
53
Parameter group 6-1* Analog Input 1
Reference
Analog input. Selectable for
voltage or current. Switches A53
and A54 select mA or V.
54
Parameter group 6-2* Analog Input 2
Feedback
55
–
–
Common for analog input
Serial communication
61
–
–
Integrated RC-filter for cable shield.
ONLY for connecting the shield
when experiencing EMC problems.
68 (+)
Parameter group 8-3 FC Port Settings
–
RS485 interface. A control card
switch is provided for termination
resistance.
69 (-)
Parameter group 8-3 FC Port Settings
–
Relays
01, 02, 03
Parameter 5-40 Function Relay
[0]
[9] Alarm
Form C relay output. Usable for AC
or DC voltage and resistive or
inductive loads.
04, 05, 06
Parameter 5-40 Function Relay
[1]
[5] Running
Table 12.1 Terminal Description
Extra terminals:
•
Two form C relay outputs. Location of the outputs depends on frequency converter configuration.
•
Terminals on built-in optional equipment. See the manual provided with the equipment option.
Control Wiring
VLT
®
Parallel Drive Modules
120
Danfoss A/S © 6/2016 All rights reserved.
MG37N102
12
12