85
VL
T
®
3500 HV
AC
MG.35.B1.02 – VL
T is a r
egister
ed Danfoss trademark
Section 1
Section 1
Section 1
Section 1
Section 1
Section 2
Section 2
Section 2
Section 2
Section 2
Section 3
Section 3
Section 3
Section 3
Section 3
Section 4
Section 4
Section 4
Section 4
Section 4
ParameterParameterParameterParameterParameter
3502
3504
3505
3508
3511
3516
3522
3532
3542
3552
3562
3575
3600
3625
3650
3700
3750
3800
103 Motor power
1.1
2.2
3.0
5.5
7.5
11
15
22
30
37
45
55
75
90
110
132
160
200
104 Motor voltage
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
105 Motor fr
equency
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
107 Motor curr
ent
2.8
5.3
6.9
12.2
15.8
22.8
31.1
42.8
59.3
72.0
86.2
106.3
134.1
166.8
197.8
230.0
272.4
345.0
109 Start voltage
39.1
36.8
36.3
35.4
35.2
35.0
34.9
34.9
36.8
36.2
36.8
36.7
36.7
36.7
36.7
36.7
36.7
36.7
202 Max. fr
equency
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
209 Curr
ent limit
2.8
5.6
7.3
13.0
16.0
24.0
31.9
44.2
61.2
73.2
88.3
105.0
139.0
168.0
205.0
243.0
302.0
368.0
215 Ramp 1 up time
5
5
5
5
15
15
15
30
30
30
30
45
45
45
45
45
45
45
216 Ramp 1 down time
5
5
5
5
15
15
15
30
30
30
30
45
45
45
45
45
45
45
217 Ramp 2 up time
5
5
5
5
15
15
15
30
30
30
30
45
45
45
45
45
45
45
218 Ramp 2 down time
5
5
5
5
15
15
15
30
30
30
30
45
45
45
45
45
45
45
232 Idle running curr
ent
1.8
2.6
3.7
5.1
5.9
9.5
11.2
14.5
22
22
30.8
38.1
44.2
59.0
66.4
74.6
85.4
105.2
308 DC brake voltage
27
28
25
14
13
11
12
11
21
20
20
0
0
0
0
0
0
0
311 T
rip delay inverter
2
2
2
2
9
9
9
12
12
12
12
0
0
0
0
0
0
0
ParameterParameterParameterParameterParameter
3502
3504
3508
3511
3516
3522
3532
3542
3552
3562
103 Motor power
1.1
2.2
5.5
7.5
11
15
22
30
37
45
104 Motor voltage
200
200
200
200
200
200
200
230
230
230
105 Motor fr
equency
50
50
50
50
50
50
50
60
60
60
107 Motor curr
ent
6.0
10.0
25.0
32.0
46.0
57.2
79.2
104.0
130
158.0
109 Start voltage
22.2
19.3
19.5
19.4
19.4
19.5
19.4
21.9
22.2
22.0
202 Max. fr
equency
50
50
50
50
50
50
50
60
60
60
209 Curr
ent limit
5.4
10.6
24.8
32.0
46.0
61.2
88.0
104.0
130.0
154.0
215 Ramp 1 up time
5
5
15
15
15
15
15
45
45
45
216 Ramp 1 down time
5
5
15
15
15
15
15
45
45
45
217 Ramp 2 up time
5
5
15
15
15
15
15
45
45
45
218 Ramp 2 down time
5
5
15
15
15
15
15
45
45
45
232 Idle running curr
ent
2.8
5.1
9.7
11.0
15.8
23.8
21.6
29.8
41.1
41.5
308 DC brake voltage
18
19
14
11
10
10
8
0
0
0
311 T
rip delay inverter
2
2
6
6
6
6
6
0
0
0
■
200/220/230 V
380/400/415 V
■
ParameterParameterParameterParameterParameter
3502
3504
3506
3508
3511
3516
3522
3532
3542
3552
3562
3575
3600
3625
3650
3700
3750
3800
103 Motor power
1.1
2.2
4
5.5
7.5
11
15
22
30
37
45
75
90
110
132
160
200
250
104 Motor voltage
460
460
460
460
460
460
460
460
460
460
460
460
460
460
460
460
460
460
105 Motor fr
equency
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
107 Motor curr
ent
2.5
4.8
7.6
10
13.7
20.0
25.0
35.5
48.5
61.8
74.9
110.8
137.8
163.4
190.0
225.0
285.0
360.0
109 Start voltage
48.6
45.8
45.2
45
44.9
44.7
44.3
43.8
44.6
44.5
47.0
47.0
47.0
47.0
47.0
47.0
47.0
47.0
202 Max. fr
equency
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
209 Curr
ent limit
2.6
4.8
8.2
12.6
14.4
21.8
27.9
41.6
54.2
65.0
78.0
96.0
124.0
156.0
180.0
240.0
302.0
361.0
215 Ramp 1 up time
5
5
5
30
30
30
30
30
30
30
30
45
45
45
45
45
45
45
216 Ramp 1 down time
5
5
5
30
30
30
30
30
30
30
30
45
45
45
45
45
45
45
217 Ramp 2 up time
5
5
5
30
30
30
30
30
30
30
30
45
45
45
45
45
45
45
218 Ramp 2 down time
5
5
5
30
30
30
30
30
30
30
30
45
45
45
45
45
45
45
232 Idle running curr
ent
2.0
3.7
4.4
5.3
6.6
10.2
11.7
12.2
17.8
22.9
23.7
36.4
48.7
54.8
61.6
70.4
86.9
104.5
308 DC brake voltage
24
23
16
11
11
9
9
9
9
9
90000000
311 T
rip delay inverter
2
5
7
7
7
7
7
8
8
1
2
1
2
0000000
■
440/460/500 V
4.7 Factory settings