86
VLT
®
3500 HVAC
MG.35.B1.02 – VLT is a registered Danfoss trademark
■
Load and motor
100
LOAD TYPE
4
)
Energy VT.L
101
SPEED CONTROL
4
)
#
)
Open loop
102
SET CUR. LIMIT
Program. value
103
MOTOR POWER
4
)
#
)
Depending on unit
104
MOTOR VOLTAGE
4
)
#
)
Depending on unit
105
MOTOR FREQ
4
)
#
)
Depending on unit
107
MOTOR CURRENT
4
)
Depending on unit
109
START VOLTAGE
4
)
Depending on unit
114
FEEDBACK TYPE
Current
115
DIS VLU@min FB
0
116
DIS VLU@max FB
100 %
117
DISPLAY UNIT
%
119
FEED FWD FACTR
4
)
100%
120
CONTRL RANGE
4
)
100%
121
PROPRT/L GAIN
4
)
0.01
122
INTEGRAL TIME
4
)
Off
123
DIFFERENTL TIME
4
)
Off
124
LOWPASS FILTER
4
)
0.0 sec.
125
FEEDBACK FACTR
4
)
100%
Operation and display
000
LANGUAGE
English
001
SETUP OPERATIO
Setup 1
002
MENU SET COPY
#
)
Do not copy
003
HAND-O-AUTO
Keypad auto
004
LOCAL SPEED
005
VALUE AT MAX
100
006
LOCAL RESET
Enable
007
LOCAL STOP
Enable
008
KEY LOCAL/HAND
Enable
009
KEY REMOT/AUTO
Enable
010
LOC REFERENCE
Enable
011
ENERGY COUNTER
No reset
012
HOUR COUNTER
No reset
014
POWERUP MODE
Loc=stop
015
SETUP PROGRAM.
Setup=P001
References and limits
201
MIN. FREQUENCY
4
)
0.0
202
MAX. FREQUENCY
4
)
Depending on unit
203
JOG FREQUENCY
4
)
10 Hz
204
DIG. REF. TYPE
4
)
Sum
205
REF. 1 DIGITAL
4
)
0
206
REF. 2 DIGITAL
4
)
0
207
REF. 3 DIGITAL
4
)
0
208
REF. 4 DIGITAL
4
)
0
209
CURRENT LIMIT
4
)
Depending on unit
210
LO FREQ. WARN
4
)
0.0 Hz
211
HI FREQ. WARN
4
)
132 Hz
212
LO CURR. WARN
4
)
0.0
213
HI CURR. WARN
4
)
I
VLT.MAX
214
RAMP TYPE
4
)
Linear
215
RAMP UP TIME
4
)
Depending on unit
216
RAMP DOWN TIME
4
)
Depending on unit
217
ALT. UP RAMP
4
)
Depending on unit
218
ALT DOWN RAMP
4
)
Depending on unit
219
FREQ. 1 BYPASS
4
)
120 Hz
220
FREQ. 2 BYPASS
4
)
120 Hz
221
FREQ. 3 BYPASS
4
)
120 Hz
222
FREQ. 4 BYPASS
4
)
120 Hz
223
BYPASS B.WIDTH
4
)
0%
224
CARRIER FREQ.
4
)
4.5 kHz
225
VAR. CARR. FREQ.
4
)
Disable *)
232
NO LOAD CURR.
4
)
Depending on unit
■
■
4
) Available in all 4 setups.
#) Can only be changed in Stop
Mode (motor stopped)
*) For VLT 3542-3562 (230 V) and
VLT 3575-3800 LOW SWFQ.LOW
4.7 Factory settings