6
VLT
®
3500 HVAC
MG.35.B1.02 – VLT is a registered Danfoss trademark
Mains supply 3 x 380/400/415 V
According to international VDE and UL/CSA
requirements
VL
VL
VL
VL
VLT
T
T
T
T type
type
type
type
type
3502
3502
3502
3502
3502 3504
3504
3504
3504
3504 3505
3505
3505
3505
3505 3508
3508
3508
3508
3508 3511
3511
3511
3511
3511 3516
3516
3516
3516
3516 3522
3522
3522
3522
3522 3532
3532
3532
3532
3532 3542
3542
3542
3542
3542 3552
3552
3552
3552
3552 3562
3562
3562
3562
3562
Output current
I
VLT,N
[A]
2.8
5.6
7.3
13.0 16.0
24.0
31.9
44.2 61.2 73.2 88.3
I
VLT,
MAX
(60 s) [A]
3.1
6.2
8.0
14.3 17.6
26.4
35.2 48.4 67.1
80.3 96.8
Output (at 415 V)
S
VLT,N
[kVA]
2.0
4.0
5.2
9.3
11.5
17.2
22.9 31.8 44.0
52.6 63.5
Typical shaft output
P
VLT,N
[kW]
1.1
2.2
3.0
5.5
7.5
11.0
15.0 22.0 30.0
37.0 45.0
Max. cable cross-section
[mm
2
]
2.5
2.5
2.5
2.5
2.5
16.0
16.0 16.0 35.0
35.0 50.0
Max. motor cable length
[m]
300, with screened cables: 150 m
5
)
Rated motor voltage
U
M,N
[V]
380/400/415
Rated motor frequency
f
M,N
[Hz]
50/60/87/100
Max. input current
I
L,N
[A]
2.8
5.6
7.3
13.0 17.0
22.0
31.0 41.5 57.5
66.5 80.0
Max. cable cross-section
[mm
2
]
2.5
2.5
2.5
2.5
2.5
16.0
16.0 16.0 35.0
35.0 50.0
Max. pre-fuses
[A]
16
16
16
25
25
50
63
63
80
100
1
) 125
1
)
Mains contactor
4)
[Danfoss type]
CI 6
CI 6
CI 9
CI 5
CI 6
CI 9
CI 16 CI 32 CI 32 CI 37 CI 45
[AC value]
AC-3 AC-3 AC-3 AC-3 AC-1 AC-1
AC-1 AC-1 AC-1 AC-1 AC-1
Supply voltage
[V]
3 x 380/400/415 ±10% (VDE 0160)
Supply frequency
[Hz]
50/60 Hz
Power factor / cos.
ϕ
1
0.9/1.0
Switching on input
times/min.
2
Power loss at max. load
[W]
60
100
130
280
300
425
580
880
1390 1875 2155
Ambient temperature
[°C]
-10
→
+40 at full load
2
)
2.1 Installation r
elated pr
oduct data
VL
VL
VL
VL
VLT type
T type
T type
T type
T type 3575
3575
3575
3575
3575
3600
3600
3600
3600
3600
3625
3625
3625
3625
3625
3650
3650
3650
3650
3650
3700
3700
3700
3700
3700
3750
3750
3750
3750
3750
3800
3800
3800
3800
3800
Output current
I
VLT,N
[A] 105
139
168
205
243
302
368
I
VLT,MAX
(60 s) [A] 116
153
185
226
267
332
405
Output (at 415 V)
S
VLT,N
[kVA] 75.5
99.9
121
147
175
217
265
Typical shaft output
P
VLT,N
[kW] 55
75
90
110
132
160
200
Max. cable cross-section
[mm
2
] 70
70
150
150
150
2 x 120
2 x 120
Terminal torque
[Nm] 6
6
10
10
10
6
6
Max. motor cable length
[m] 300
Rated motor voltage
U
M,N
[V] 380/400/415/440/460/500
Rated motor frequency
f
M,N
[Hz] 50/60/87/100
Max. input current
I
L,N
[A] 103.3
138.4
167.2
201.7
241.9
293.3
366.3
I
L,MAX
(60 s) [A] 116
153
185
226
267
332
405
Max. cable cross-section
[mm
2
] 120
120
2 x120
2 x120
2 x120
2 x 240
2 x 240
Terminal troque
[Nm] 31.1
31.1
31.1
31.1
31.1
42
42
Pre-fuses
3
)
[A] 150
150
250
250
300
450
500
Mains contactor
4)
[Danfoss type] CI 85
CI 85
CI 140
CI 140
CI 140
-
-
[AC value] AC-1
AC-1
AC-1
AC-1
AC-1
-
-
Supply voltage (VDE 0160)
[V] 3 x 380/400/415/440/460/500 ±10%
Supply frequency
[Hz] 50/60
Power factor / cos.
ϕ
1
0.9/1.0
Switching on input
times/min. 1
Power loss at max.
Front 529
713
910
1091
1503
1812
2209
load [W]
Heat sink 1074
1447
1847
2216
3051
3679
4485
Ambient temperature
[°C] –10
→
+40 at full load
2
)
1
)
Only semi-conductor fuses
2
)
In the range -10 to 0°C, the equipment can start and run; however, the display values and
certain operating characteristics will not fulfil the specifications.
3
)
Bussmann rapid type JJS integrated.
4
)
If mains contactors are used, the following Danfoss types are recommended:
Max. ambient tempe40°C
5
)
VLT 3502-3505 fswitch > 4,5 kHz; max. 40 m motor cable.
■