Danfoss Electronics spa
Air Handling
seq.- user manual
DKRCC.PS.RI.A1.02 / 520H4358 - Air Handling Seq. user manual - V 2.2
Produced by Danfoss Electronics spa Graphic Department, 10-2009
65
TABLE OF EXPORTED VARIABILES 1
Code
Description
Notes
R/W
Register
Address
Cool1 Req. Power
R
43
Humidifier Req. Power
R
44
Dehumidifier Req. Power
R
45
Reserved
R
46
Parameters
first parameter
See Configurator
R/W
8194
......
Analog inputs (function)
Not Used
9249
SUP
Supply Temp
Supply air temperature
R
9250
REt
Return Temp
Return air temperature
R
9251
OUt
Outside Temp
Outside air temperature
R
9252
tH1
Preheat Temp
Pre-heating temperature
R
9253
tH2
Reheat Temp
Reheat Temp
R
9254
tC1
Cooling Temp
Cooling temperature
R
9255
tC2
AntiFreeze
Antifreeze temperature
R
9256
bAR
Air Pressure
Air pressure
R
9257
SHU
Sup. Humidity
Supply air humidity
R
9258
RHU
Ret. Humidity
Return air humidity
R
9259
CO2
CO2
Air carbon dioxide (CO2) measurement
R
9260
VOC
VOC
Air volatile organic compounds (VOC)
measurement
R
9261
Analog outputs (function)
Not Used
10065
SUF
Supply Fan
Supply Fan control
R
10066
REF
Return Fan
Return Fan control
R
10067
RDA
Mixing damper
Mixing damper control
R
10068
EDA
External Damper
External damper control
R
10069
HUA
Humidifier
Humidifier control
R
10070
bA1
Valve1
Valve 1 control
R
10071
bA2
Valve2
Valve 2 control
R
10072
bA3
Valve3
Valve 3 control
R
10073
DHU
Dehumidifier
Dehumidifier control
R
10074
ERA
Recovery
Energy recovery control
R
10075
Internal variables
Reserved
R
16641 - 16648
Main set heat
R
16649
Main set cool
R
16650
Cascade set heat
R
16651
Cascade set cool
R
16652
Reserved
R
16653-16657
Heating1 Req. Power B1
R
16658
Heating1 Req. Power B2
R
16659