DKRCC.PS.RI.A1.02 / 520H4358 - Air Handling Seq. user manual - V 2.2
Produced by Danfoss Electronics spa Graphic Department, 10-2009
18
Danfoss Electronics spa
Air Handling seq.
- user manual
It is possible to configure more coils controlled with the same control sequence. In this case they share equally the
control band.
Example
* Three coils for heating
controlled with Heat Sequence 1;
b10=b40=b70=HS1
Fig 6 _ [Coils control - example heat sequence]
4.2| Coil output management
The following parameters set the way coil output are managed according to the load demand calculated by the
associated temperature control sequences
(see “6.2] Heat and cool control sequences”)
.
COIL OUTPUT MANAGEMENT
COI
Coils
Min
Max
Default
U.M.
Text value
CL1
Coil 1
b11
Actuator 1 type
1
4
VALVE
VALVE;LIN STEP;VAR STEP;BIN
STEP
CL2
Coil 2
b41
Actuator 2 type
1
4
LIN STEP
VALVE;LIN STEP;VAR STEP;BIN
STEP
CL3
Coil 3
b71
Actuator 3 type
1
4
LIN STEP
VALVE;LIN STEP;VAR STEP;BIN
STEP
Tab 10_ [Coils control -Coil output management]
Through b11, b41, b71 you can define the actuator type for each coil, whether it is a water coil controlled trough a
valve or it is a step controlled coil (e.g. electric resistances). In this case there are 3 possible way of control: linear step
switch, variable step switch binary step switch.