6.4| Main setpoint
MAIN SETPOINT
SET
Setpoint
Min
Max
Default
U.M.
Text value
MST
Main Setpoint
STH
Setpoint heat
-15,0
90,0
21,0
°C
STC
Setpoint cool
-15,0
90,0
21,0
°C
HUM
Min setpoint humidity
0
100,0
40,0
%
DEH
Max setpoint humidity
0
100,0
60,0
%
EST
Economy Setpoint
ES1
Economy set enable
1
2
NO
NO;YES
ES2
Offset set heat economy
-15,0
90,0
-3,0
°C
ES3
Offset set cool economy
-15,0
90,0
2,0
°C
COM
TempCompensation
TC1
Probe selection
1
8
OUt
NO;SUP;REt;OUt;tH1;tH2;tC1;tC2
TC2
Winter end temperature
-15,0
90,0
-5,0
°C
TC3
Winter start temperature
-15,0
90,0
5,0
°C
TC4
Winter offset
-10,0
10,0
-2,0
K
TC5
Summer start temperature
-15,0
90,0
31,0
°C
TC6
Summer end temperature
-15,0
90,0
38,0
°C
TC7
Summer offset
-10,0
10,0
7,0
K
Tab 26_ [Temperature control sequences - Main setpoint]
The main temperature setpoint are STH for heating and STC for cooling temperature control.
The active temperature setpoint (hereafter ATS) is then:
ATS=STH in heating
ATS=STC in cooling
Through parameters D02, D03, H12, H22, C12, they can be assigned to the specific sequence,
(see “6] Temperature control sequences”)
.
The main humidity setpoint are HUM for humidifying and DEH for dehumidifying control.
Main setpoint are accessible from the user interface in an shorten way, by pressing the DOWN key for 3 seconds.
Main setpoint are affected by economy mode and temperature compensation
6.4.1|
Economy mode
The economy mode can be enabled by ES1=YES or via digital input “COE – Comf/Eco”.
By enabling the economy mode, the main temperature setpoint are changed by ES2 and ES3 quantity.
The Active Temperature Setpoint (ATS) becomes:
ATS=STH+ES2 in heating
ATS=STC+ES3 in cooling