Danfoss Electronics spa
Air Handling
seq.- user manual
DKRCC.PS.RI.A1.02 / 520H4358 - Air Handling Seq. user manual - V 2.2
Produced by Danfoss Electronics spa Graphic Department, 10-2009
61
TABLE OF EXPORTED VARIABILES 1
Code
Description
Notes
R/W
Coil Address
RFW
Return Flow
Return flow alarm
R
13
SFI
Supply Filter
Supply air filter plugged
R
14
RFI
Return Filter
Return air filter plugged
R
15
PU1
Coil1 Pump
Coil 1 pump alarm
R
16
PU2
Coil2 Pump
Coil 2 pump alarm
R
17
PU3
Coil3 Pump
Coil 3 pump alarm
R
18
HUM
HumidifierAlarm
Humidifier alarm
R
19
REC
RecoveryAlarm
Energy recovery alarm
R
20
GEN
Generic Alarm
Generic alarm
R
21
bA1
Coil1 Alarm
Coil 1 alarm
R
22
bA2
Coil2 Alarm
Coil 2 alarm
R
23
bA2
Coil3 Alarm
Coil 3 alarm
R
24
LOF
Lock Fan
Lock/Unlock fans
R
25
COE
Comf/Eco
Comfort/Economy selection
R
26
FDI
FreeHeatCool
Freeheat/Freecool changeover
R
27
Not Used
28 - 64
Digital Output
Not Used
65
ALA
Alarm
Alarm
R
66
WAR
Warning
Warning
R
67
SUF
Supply Fan
Supply Fan control
R
68
REF
Return Fan
Return Fan control
R
69
RDD
Mixing Damper
Mixing Damper control
R
70
EDD
External Damper
External Damper control
R
71
SFL
SupplyFanLow
Low Supply Fan speed
R
72
SFH
SupplyFanHigh
High Supply Fan speed
R
73
RFL
ReturnFanLow
Low Return Fan speed
R
74
RFH
ReturnFanHigh
High Return Fan speed
R
75
dEU
Dehumidifier
External dehumidifier control
R
76
HUM
Humidifier
External humidifier control
R
77
HUP
HumPump
Humidifier pump control
R
78
ERD
Recovery
Energy recovery control
R
79
ERP
Recovery Pump
Energy recovery pump control
R
80
b1
Valve1ONOFF
Controls the ON/OFF valve of coil 1
R
81
b1O
Valve1Open
Controls opening of 3-point valve of coil 1
R
82
b1C
Valve1Close
Controls closing of 3-point valve of coil 1
R
83
b11
Coil1Step1
Controls step 1 of coil 1
R
84
b12
Coil1Step2
Controls step 2 of coil 1
R
85
b13
Coil1Step3
Controls step 3 of coil 1
R
86
CP1
Coil1Pump
Coil1 pump control
R
87
b2
Valve2ONOFF
Controls the ON/OFF valve of coil 2
R
88
b2O
Valve2Open
Controls opening of 3-point valve of coil 2
R
89
b2C
Valve2Close
Controls closing of 3-point valve of coil 2
R
90
b21
Coil2Step1
Controls step 1 of coil 2
R
91
b22
Coil2Step2
Controls step 2 of coil 2
R
92
b23
Coil2Step3
Controls step 3 of coil 2
R
93