Danfoss Electronics spa
Air Handling
seq.- user manual
DKRCC.PS.RI.A1.02 / 520H4358 - Air Handling Seq. user manual - V 2.2
Produced by Danfoss Electronics spa Graphic Department, 10-2009
63
TABLE OF EXPORTED VARIABILES 1
Code
Description
Notes
R/W
Coil Address
A11
Supply filter alarm
0=OFF, 1=ON
R
188
A12
Return filter alarm
0=OFF, 1=ON
R
189
A13
Pump 1 overload
0=OFF, 1=ON
R
190
A14
Pump 2 overload
0=OFF, 1=ON
R
191
A15
Pump 3 overload
0=OFF, 1=ON
R
192
A16
Coil 1 alarm
0=OFF, 1=ON
R
193
A17
Coil 2 alarm
0=OFF, 1=ON
R
194
A18
Coil 3 alarm
0=OFF, 1=ON
R
195
A19
Humidifier alarm
0=OFF, 1=ON
R
196
A20
Recovery alarm
0=OFF, 1=ON
R
197
A21
General alarm
0=OFF, 1=ON
R
198
AEX
No connection with EXC Module
0=OFF, 1=ON
R
199
E01
Analog Input 1 fault
0=OFF, 1=ON
R
200
E02
Analog Input 2 fault
0=OFF, 1=ON
R
201
E03
Analog Input 3 fault
0=OFF, 1=ON
R
202
E04
Analog Input 4 fault
0=OFF, 1=ON
R
203
E05
Analog Input 5 fault
0=OFF, 1=ON
R
204
E06
Analog Input 6 fault
0=OFF, 1=ON
R
205
E07
Analog Input 7 fault
0=OFF, 1=ON
R
206
E08
Analog Input 8 fault
0=OFF, 1=ON
R
207
E09
Analog Input 9 fault
0=OFF, 1=ON
R
208
E10
Analog Input 10 fault
0=OFF, 1=ON
R
209
E11
Analog Input 11 fault
0=OFF, 1=ON
R
210
E12
Analog Input 12 fault
0=OFF, 1=ON
R
211
E13
Analog Input 13 fault
0=OFF, 1=ON
R
212
E14
Analog Input 14 fault
0=OFF, 1=ON
R
213
E15
Analog Input 15 fault
0=OFF, 1=ON
R
214
E16
Analog Input 16 fault
0=OFF, 1=ON
R
215
Tab 42_ [Modbus Communication - Table of exported variabiles 1 ]
TABLE OF EXPORTED VARIABILES 1
Code
Description
Notes
R/W
Register
Address
Digital inputs (physical values)
Digital input
bit 0 (0000 0000 0000 0001) -> Digital input 1
...
bit 15 (1000 0000 0000 0000) -> Digital input 16
R
1
Digital input
bit 0 (0000 0000 0000 0001) -> Digital input 17
...
bit 15 (1000 0000 0000 0000) -> Digital input 32
R
2
Digital outputs (physical values)
Digital output
bit 0 (0000 0000 0000 0001) -> Digital output 1
...
bit 15 (1000 0000 0000 0000) -> Digital output 16
R
3