DKRCC.PS.RI.A1.02 / 520H4358 - Air Handling Seq. user manual - V 2.2
Produced by Danfoss Electronics spa Graphic Department, 10-2009
62
Danfoss Electronics spa
Air Handling seq.
- user manual
TABLE OF EXPORTED VARIABILES 1
Code
Description
Notes
R/W
Coil Address
CP2
Coil2Pump
Coil2 pump control
R
94
b3
Valve3ONOFF
Controls the ON/OFF valve of coil 3
R
95
b3O
Valve3Open
Controls opening of 3-point valve of coil 3
R
96
b3C
Valve3Close
Controls closing of 3-point valve of coil 3
R
97
b31
Coil3Step1
Controls step 1 of coil 3
R
98
b32
Coil3Step2
Controls step 2 of coil 3
R
99
b33
Coil3Step3
Controls step 3 of coil 3
R
100
CP3
Coil3Pump
Coil3 pump control
R
101
dEF
Defrost
Defrost activation
R
102
HRE
HeatRequest
Request of heating
R
103
CRE
CoolRequest
Request of cooling
R
104
Not Used
105 - 128
Device state
Standby Device State
0=ON, 1=OFF
R/W
129
Alarm Device State
0= not in alarm mode, 1=in alarm mode
R
130
Alarms recognized
0=YES, 1=NO
R
131
Summer/Winter
0=Summer, 1=Winter
R
132
Reserved
R
133
Lock Fans
0=Unlocked, 1=locked
R
134
Frost Protection
0=NO, 1=YES
R
135
Not Used
136 – 144
Status Supply FAN
0=OFF, 1=ON
R
145
Status Return FAN
0=OFF, 1=ON
R
146
Reserved
R
147 - 155
Status Damper FreeCooling
0=OFF, 1=ON
R
156
Status Damper FreeHeating
0=OFF, 1=ON
R
157
Reserved
158 – 169
Status Pumps
0=OFF, 1=ON
R
170
Status Recovery FreeCooling
0=OFF, 1=ON
R
171
Status Recovery FreeHeating
0=OFF, 1=ON
R
172
Status Humidifier
0=OFF, 1=ON
R
173
Status Dehumidifier
0=OFF, 1=ON
R
174
Not Used
175 - 176
Alarms
Not Used
177
A01
Supply fan alarm
0=OFF, 1=ON
R
178
A02
External damper locked
0=OFF, 1=ON
R
179
A03
Supply fan safety switch
0=OFF, 1=ON
R
180
A04
Return fan alarm
0=OFF, 1=ON
R
181
A05
Mixing damper locked
0=OFF, 1=ON
R
182
A06
Return fan safety switch
0=OFF, 1=ON
R
183
A07
Freeze alarm
0=OFF, 1=ON
R
184
A08
Fire alarm
0=OFF, 1=ON
R
185
A09
Supply air flow alarm
0=OFF, 1=ON
R
186
A10
Return air flow alarm
0=OFF, 1=ON
R
187