6 Application Examples
6.1 Homing
Function
Digital control
mode
Fieldbus
mode
Quick bus
(Fieldbus mode)
Homing
IN 9
PCD[1].3
PCD[1].3
Clear home
status
IN 6
PCD[1].6
PCD[1].6
Table 6.1 Homing Signals
NOTICE
Connect the homing switch to IN 4 and select the
sequence in parameter
33-04 Behaviour during Home
Motion
.
6.2 Touch Probe Positioning
The target position is calculated relative to the actual
position, after the touch probe input is activated.
Similar configuration like relative/absolute positioning, but:
Parameter
19-28 Index Trajectory Type
must be either
positive (2) or negative (3)
By using quick bus: PCD[1].13 (positive) / PCD[1].14
(negative)
Parameter 19-03 Touch Probe Delay
in ms.
Operating mode
Function
Digital
control mode
Fieldbus
mode
Quick bus
(Fieldbus
mode)
Start positioning IN 5
PCD[1].5
PCD[1].1
Position reached OUT 2
PCD[1].2
PCD[1].2
Reset touch
probe
IN 7
PCD[1].7
PCD[1].7
Table 6.2 Operating Mode
6.3 Brake Control
Important parameters:
•
19-09 Automatic Break Control
•
19-10 Coast Delay
•
19-11 Brake Delay
•
19-12 Hold Delay
•
19-13 Brake Wear Limit
If the application is not equipped with an electrome-
chanical brake, these parameters are not relevant.
However, it is important to set parameter
19-09 Automatic
Brake Control
to
[0] Disabled
to enable the motor also at
standstill.
Start procedure:
After
start positioning
is activated, the mechanical brake is
opened after the time selected in
19-11 Brake Delay
. This
time delay is to ensure that the motor is fully magnetised
when the brake is released, preventing the load from
dropping after start.
130BB996.10
Time
Time defined in P 19-11
Start magnetizing the
motor [MOTOR ON]
Brake closed
Start
Start positioning
Brake opened
Illustration 6.1 Brake Delay
Stop procedure:
At
position reached
the delay selected in
19-10 Coast Delay
ensures that the brake is closed when the controller coasts
the motor.
130BB997.10
Time
Time defined in P 19-11
Position reached
Motor stop - Brake closed
Stop
Motor
demagnetized
Illustration 6.2 Coast Delay
Application Examples
Operating Instructions
42