7.2.2 1000h Device Type
This object describes the type of device and its
functionality. It is composed of a 16-bit field describing the
device profile used, and a second 16-bit field providing
additional information about optional functionality of the
device.
Additional Information
Device Profile
Number
Mode Bits Type Bits
Bits
31..
24
23..
16
15..
0
0
1 (frequency converters, DS402) 402
0
1 (frequency converters,
Danfoss)
-1
Table 7.2 1000h Device Type
Device type will show 0x10192 when DS402 profile is
selected in frequency converter, and 0 in case of FC profile.
7.2.3 1001h Error Register
This object is the error register of the device. Only bit 0 is
supported. The other information of errors is read with
object 603Fh.
Bit
Meaning
0
Generic error
Table 7.3 1001h Error Register
7.2.4 1002h Manufacturer Status Register
The contents of this object are manufacturer specific, and
inform of the state of the frequency converter:
Value
Meaning
1
Init
2
Pre-operational
3
Boot
4
Safe-operational
5
Operational
Table 7.4 1002h Manufacturer Status Register
7.2.5 1003h Predefined Error Field
Holds the error on the frequency converter. Setting index 0
to 0 erases the field. Disabling the diagnosis trigger (FC
p807) disables the display of values in this object (that is,
they stay at 0).
Index
Meaning
1003h 0
Number of stored errors
1003h 1
Current error
Table 7.5 1003h Predefined Error Field
The current error consist of two 16 bit word, where the
most significant word holds the information if a warning or
alarm is set.
Bit0
1, Alarmword 1 has an active Alarm (
16-90 Alarm Word
)
Bit1
1, Alarmword 2 has an active Alarm (
16-91 Alarm Word
2
)
Bit2
0, Reserved
Bit3
1, Warningword 1 has an active Warning (P 16-92)
Bit4
1, Warningword 2 has an active Warning (P 16-93)
Bit5-15 0, Reserved
Table 7.6
The least significant word reflects the following possible
errors:
Code (hex)
Meaning
0
No fault
1000
General fault
2130
Short circuit
2213
Overcurr. during startup
2240
Short to earth
2310
Continuous overcurrent
2311
Current inside the device, no. 1
3100
Mains voltage
3130
Phase failure
3210
Overvoltage inside the device
3220
undervoltage inside the device
3300
Output voltage
4210
Exceed device temperature
4310
Excess frequency converter temperature
5110
Low voltage power supply
5112
+24 V power supply
5210
Measurement circuit
6100
Internal software fault
7110
Brake chopper
8100
Communication
8302
Torque limiting
Table 7.7
7.2.6 1008h Manufacturer Device Name
This object contains the device name as defined in
15-40 FC Type
.
Communication Profile Area
MCA 124 EtherCAT Operating Instruction
26
MG92A302 - VLT
®
is a registered Danfoss trademark
7
7