Bit 05, Quick stop/Run
Bit 05="0" - control word bit 02="1".
Bit 05="1" - control word bit 02="0".
Bit 06, Start enable/Start disable
Bit 06="0" - state is not “Switch on disable”.
Bit 06="1" - state = “Switch on enable”.
Bit 07, No warning/Warning
Bit 07="0" - no warning situation.
Bit 07="1" - a warning has occurred.
Bit 08, Danfoss reserved:
Bit 09, Remote disable/Remote enable
Bit 09="0" - the frequency converter has been stopped
with the stop key on the LCP, or [Local] has been selected
in
3-13 Reference Site
.
Bit 09="1" - it is possible to control the frequency
converter via the serial port.
Bit 10, Set point not reached/Set point reached
Bit 10="0" - the actual motor speed is different from the
speed reference set. This situation can occur while the
speed is ramped up/down during start/stop.
Bit 10="1" - the present motor speed equals the speed
reference set.
Bit 11, Speed limit not active/speed limit active
Bit 11="0" - the output frequency is out of the range set in
parameters 4-11/4-12
Motor Speed low Limit RPM/Hz
or
parameters 4-13/4-14
Motor Speed high Limit RPM/Hz
.
Bit 11="1" - the output frequency is within the mentioned
range.
Bit 12, DSP 402 reserved
Bit 13, DSP 402 reserved
Bit 14, Running/Not running
Bit 14="0" - the motor is not running.
Bit 14="1" - the frequency converter has a valid start signal
or that the output frequency is greater than 0 Hz.
Bit 15, Danfoss reserved.
8-10 Control Profile
Option:
Function:
[0]
*
FC profile
[7]
CANopen DSP 402
FC Profile
is the default control profile for the frequency
converter, whereas
CANopen DSP 402
is the CiA
standardized control profile, featuring the special DSP 402
transition state machine.