m Version 3.11
Manual RS.8A.N5.0 © Danfoss 10-007
33
Choice of measurements to be displayed as pri-
mary and secondary:
Select the menu: Setup Menu \ Point Setup
Number:
Select the point number (i.e. address
number of EKC)
Type:
Select “EKC”
Alarms:
Will always be “Remote”. The alarm limits
for the controller will be used.
Other settings are those normally used for m.
Next menu
Press and hold down the ‘
Enter
’ key until the second Point Setup screen is
displayed or press the ' ' in the point type field.
Input Source:
Select “ECHELON” (= data communication)
Primary Temp:
Used to select the parameter to be displayed
as primary
Secndary Temp:
Used to select the parameter to be displayed
as secondary
Other settings are those normally used for m.