m Version 3.11
Manual RS.8A.N5.0 © Danfoss 10-007
13
The various codes printed in the status (St) column are defined as follows:
ok
No fault present
Alm
Equipment fault
dEF
Defrost
dEP
Defrost pulldown - (only shown on display)
dFP
Defrost pulldown - (only shown on printouts)
E
Equipment (status ok)
Err
Equipment (status alarm)
Flt
Comms fault
Hi
High alarm
Inh
Inhibit
Low
Low alarm
Off
The input is off
OVR
Defrost overrun alarm
OC
Signal over range
SC
Signal under range
The various codes displayed in the printout Reason column are defined as
follows:
Aft.Def
Alarm after defrost
Fault
probe fault
>
High value alarm greater than high alarm limit
<
Low value alarm less than low alarm limit.
Use this option to display the units software and hardware details for reference.
To return to the Main Menu, either wait 1 minute or press any key.
To set the system time and date, select the Time / Date option from the Main
Menu. The Password request is displayed. Enter your User passcode (the
default passcode is WOODLEY or the Local passcode).
Use ‘ ’ or ‘ ’ keys to cycle through the character list to the required value and
the ‘ ‘ or ‘ ‘ key to move the cursor left or right respectively. Then press ‘
↵
’
to
move onto the next field.
The system time and date are read from the internal clock. If these are incorrect
amend them as appropriate.
The Start Day and End Day settings are used to indicate the start and end of
trading. This allows the system to perform different operations depending on
the time of day.
For example, the system could be set up so that during the day only an audible
alarm is activated, whereas the system would dial-out at night.
Select each of the days in turn and type in or amend the times as required.
·
Use the ‘ ’ or ‘ ’ keys to cycle through the day of the
week and the special days.
·
Set the Start and End day values.
·
Set the date of any Special Days (dd/mm) (5 Special
Days maximum).
The Special Days are used to override the normal weekday start and end times.
Note:
The Special Days will occur every year if they are not changed.
Software Version
Setting the System Time and Date