EN
Installation Guide
Danfoss
Icon™
Master Controller 24 V
Master Controller 24V and Expansion Module (optional)
Supply voltage
220-240 V AC
Supply frequency
50/60 Hz
Output voltage, actuators
24 V DC
Max . power consumption per actuator output
2 W
Number of actuator outputs (1 actuator per output terminal)
10 or 15 depending on type
Output voltage, thermostats
24 V DC
Stand-by consumption per thermostat
0,2 W
Max . number of thermostats
10 or 15 depending on type
Max . length of wire from master controller to a 24 V thermostat
(depends on cable type used)
If 2x2x0,6 mm² STP/UTP: 100 m
If 2x0,5 mm²: 150 m
If > 2x0,75 mm²: 200 m
Stand-by consumption, Master Controller
< 2 W
Max . power consumption, excluding use of PWR 1 and PWR 2
outputs
< 50 W
Internal protection (fuse, non-replacable)
2,5 A
Output “Relay”
Micro-disconnection (Type 1 .B action), Max . 2 A load
Actuator outputs, type
Electronic disconnection (Type 1 .Y action)
Output “PWR 1”, type and rated max . output
Micro-interruption (Type 1 .C action)
Output “PWR 2”, type and rated max . output
Type: Permanent output, Always live 230 V, Max . 50W
Output “PWR 3” (optional, on Expansion module — used for dew
point sensor)
24 V DC, max . 1 W
Input “1”
(optional, on Expansion module — use varies acc. to
application chosen)
Ext . switch input (internal 24 V pull-up)
Input “2”
(optional, on Expansion module — use varies acc. to
application chosen)
Ext . switch input (internal 24 V pull-up)
Input “3”, sensor input
(optional, on Expansion module)
External sensor, PT 1000 (Danfoss ESM 11)
Dimensions
W: 370 mm, H: 100 mm, D: 53 mm
Conformity declared acc . to following directives
LVD, EMC, RoHS and WEEE
Purpose of control
Individual electronic room temperature control
Method of providing earthing
Factory fitted power cord, incl . PE-conductor
Encapsulation (IP Class)
IP 20
Protection class
Class I
Ambient temperature range, continious use
0 °C to + 50 °C
Wireless Thermostat
Purpose of control
Room thermostat for room temperature control
Ambient temperature range, continious use
0 °C to + 40 °C
Frequency
869 MHz
Transmission power
<2,5 mW
Encapsulation (IP Class)
IP 21
Supply voltage
2 x 1,5 V AA-Alkaline batteries
Conformity declared acc . to following directives
RED, RoHS, WEEE
Protection class
Class III
24V Wired Thermostat
Purpose of control
Room thermostat for room temperature control
Ambient temperature range, continious use
0 °C to + 40 °C
Encapsulation (IP Class)
IP 21
Supply voltage
24 V DC
Conformity declared acc . to following directives
EMC, RoHS, WEEE
Protection class
Class III
External sensor
NTC type, 47 k @ 25 °C (Optional, 088U1110)
VIMCG30F | 088N3678 | 13
© Danfoss | FEC | 2019 .02
Summary of Contents for Icon Master
Page 1: ...Installation Guide Danfoss Icon Master Controller 24 V www danfoss com ...
Page 2: ......
Page 104: ...24V 104 Danfoss FEC 2019 02 VIMCG30F 088N3678 ...
Page 106: ... M 106 Danfoss FEC 2019 02 VIMCG30F 088N3678 ...
Page 107: ...CN 088U1103 2 VIMCG30F 088N3678 107 Danfoss FEC 2019 02 ...
Page 108: ...OK M 108 Danfoss FEC 2019 02 VIMCG30F 088N3678 ...
Page 109: ...CN VIMCG30F 088N3678 109 Danfoss FEC 2019 02 ...
Page 110: ...OK 110 Danfoss FEC 2019 02 VIMCG30F 088N3678 ...
Page 111: ...CN OK VIMCG30F 088N3678 111 Danfoss FEC 2019 02 ...
Page 112: ...112 Danfoss FEC 2019 02 VIMCG30F 088N3678 ...
Page 113: ...CN VIMCG30F 088N3678 113 Danfoss FEC 2019 02 ...