Installation Guide
Danfoss
Icon™
Master Controller 24 V
Keys
1.
Installer key
Used by the installer when setting up the system (used during installation) .
• Select
INSTALL
for installing and configuring the system .
• Select
UNINSTALL
for replacing or removing a system component, e .g . a thermostat .
• Select
TEST
for finalizing the installation and to run one of three test types, either: Network test, Application test or Flow test
(i .e . flushing of system)
• Select
RUN
when all system devices are installed and a TEST is finished .
2.
Mode key
Used for choosing the desired control behavior of the entire system (set once for the entire system) .
• PWM+:
Type of regulation designed to minimize overheating by dividing the heat demand into smaller bits (= duty cycles) . The
length of a duty cycle varies depending on the chosen heat emitter . PWM+ also features auto balancing of flow to the different
rooms, which improves the heating comfort .
• On/Off:
A simple hysteresis control, which turns on the heat when the temperature is below the desired room temperature .
The heat will not be turned off until the desired room temperature is reached .
3.
Heat emitter key
Defines which heat emitter is used on the output (optimized control performance for each heat emitter type) .
• Select
SLOW
for floor construction with >50 mm concrete over pipes (typically no heat distribution panels used) .
• Select
MEDIUM
for floor or wall construction with <50 mm concrete over pipes (typically pipes laid onto heat distribution
panels) .
• Select
FAST
for radiator or convector (supplied from a manifold) .
4.
M
Actuator type selector key
Used to define which kind of 24 V actuator is used (set once for the entire system) .
• Select
NC
for normally closed (typically used) .
• Select
NO
for normally open (rarely used) .
5.
Main user interface
• Press
OK
to confirm a setting .
• Press
or
to change a parameter value or toggle through menus .
• Use
to go one step backwards in a menu .
6.
Output selector keys
Used for assigning actuator outputs to a thermostat .
• Connect only one actuator wire per output terminal.
• Assign as many outputs as you want to a thermostat .
Depending on
Danfoss
Icon
™
Master Controller model, you will have 10 or 15 outputs available .
Cable terminals
7.
Upper terminal row
For connection of 24 V thermal actuators
max. one actuator per output terminal.
8.
Lower terminal row
For connection of 24 V thermostats in a wired system, or for additional 24 V wired thermostats in a wireless system .
9.
Upper cable strain relief bar
Installed as final step of wiring, tighten screws to assure wire retention .
10. Lower cable strain relief bar
Clicks over thermostat cables to hold them in place . Top of this part also acts as cable holder for actuator cables .
11. Removable lid
Covers access to the 230 V section of
Danfoss
Icon
™
Master Controller 24V . Remove the screw and slide out to access 230 V termi-
nals . This part can be replaced with the Expansion Module, if special applications are necessary .
Connectors
12. Radio Module connector (RJ 45)
Connect the Radio Module to this connector via cat . 5 patch cable (supplied with the Radio Module) .
13. App Module connector (RJ 45)
Connect the App Module to this connector via cat . 5 patch cable (supplied with the APP Module) .
14. 3-pole connector
–
for linking together multiple Master Controllers in a 24V system.
Only used in wired systems! Loose 3-pole male connector supplied with the product .
6 | © Danfoss | FEC | 2019 .02
VIMCG30F | 088N3678
Summary of Contents for Icon Master
Page 1: ...Installation Guide Danfoss Icon Master Controller 24 V www danfoss com ...
Page 2: ......
Page 104: ...24V 104 Danfoss FEC 2019 02 VIMCG30F 088N3678 ...
Page 106: ... M 106 Danfoss FEC 2019 02 VIMCG30F 088N3678 ...
Page 107: ...CN 088U1103 2 VIMCG30F 088N3678 107 Danfoss FEC 2019 02 ...
Page 108: ...OK M 108 Danfoss FEC 2019 02 VIMCG30F 088N3678 ...
Page 109: ...CN VIMCG30F 088N3678 109 Danfoss FEC 2019 02 ...
Page 110: ...OK 110 Danfoss FEC 2019 02 VIMCG30F 088N3678 ...
Page 111: ...CN OK VIMCG30F 088N3678 111 Danfoss FEC 2019 02 ...
Page 112: ...112 Danfoss FEC 2019 02 VIMCG30F 088N3678 ...
Page 113: ...CN VIMCG30F 088N3678 113 Danfoss FEC 2019 02 ...