Refrigerants

Applicable to HCFC, non flammable HFC, 

R717 (Ammonia) and R744 (CO

2

). 

The use of ICF valve stations with flammable 

hydrocarbons is not recommended.

The ICF is only recommended for use in 

closed circuits. For further information 

please contact Danfoss.

Temperature range

-60 – 120 °C / -76 – 248 °F

Pressure range

The ICF is designed for a max. working 

pressure of 52 bar g / 754 psi g.

Application

The ICF can be used in suction, liquid, 

hotgas and liquid/vapor lines. The ICF 

regulates the flow of the medium by 

modulation or on/off function, depending 

on function modules installed in the ICF.

Regulating range

Dependent on the chosen type and 

combination of modules installed in the 

valve. 

Orientation (fig. 1)

The ICF must be installed according to  

fig. 1. The ICF must be installed with the 

arrow in the direction of the flow). 

The ICF will be delivered with all the 

function modules fully assembled. The 

modules can be taken out for service 

or inspection and may be rotated 4 x 

90° in relation to the valve body upon  

installation (fig. 1b).

The ICF is designed to withstand a high 

internal pressure. However, the piping 

system should be designed to avoid liquid 

traps and reduce the risk of hydraulic 

pressure caused by thermal expansion. 

It must be ensured that the ICF is protected 

from pressure transients like “liquid 

hammer” in the system.

Welding (fig. 2 and 3)

The ICF valve station can be welded by 

using either TIG/MIG/SMAW welding (fig. 2) 

or gas welding (fig. 3).

Always keep inlet and outlet protecting 

caps on the valve until the valve is ready 

to be installed, in order to prevent rust 

formation inside the valve station.

TIG/MIG/SMAW welding

It is not necessary to remove any of the 

function modules prior to TIG/MIG/SMAW 

welding (fig. 2) and auxiliary cooling is not 

needed at normal heat impact.

Every precaution must be taken to 

minimize welding spatter.

To avoid any welding spatter entering the 

valve station and to avoid heat impact 

to the Teflon seat during welding, it is 

recommended to open the valves slightly 

(approx. 1 turn from closed position) in first 

and last module (M1 and M4).

When welding is completed it is 

recommended to close the 2 modules 

again (M1 and M4) in order to protect the 

interior of the valve until the system is 

ready for operation. 

Gas welding

Remove all inserts before welding (fig. 3). 

Auxiliary cooling is not needed at normal 

heat impact.

Every precaution must be taken to 

minimize welding spatter.

After welding, clean the valve inside for 

welding spatter and welding debris.

It is recommended to reinstall the modules 

right after welding and to close the 2 

modules again (M1 and M4) in order to 

protect the interior of the valve until the 

system is ready for operation.

In case the valve is not assembled 

immediately make sure that rust protective 

oil is applied to the inside surfaces.

Mounting of valves 

-  Make sure that piping into which a valve 

  is installed is properly supported and 

  aligned square and plumb to the joining 

 sections. 

-  Ensure that the finalized valve assembly 

  is free of any stresses from external loads. 

-  Use only new gaskets manufactured by 

  Danfoss.  

-  Ensure that installed valves are properly 

  pressure tested, leak tested, evacuated 

  before charging with refrigerant in 

  accordance with ANSI /IIAR 5, EN378-2 or 

  ISO 5149-2.

The enclosed valves must not be mounted 

in systems where the outlet side of the 

valve is open to atmosphere. The outlet 

side of the valve must always be connected 

to the system or properly capped off, for 

example with a welded-on end plate.

Side port connections (fig. 12)

The ICF features 2 groups of 2 individual 

side ports. The 2 smaller ports P1 and 

P3 are intended for service devices like 

service valve, gauge or sight glass, while 

the bigger ports P2 and P4 can be used for 

defrost drain from the evaporator when 

doing defrost (typically hot gas).

P2 and P4 can be converted to side ports 

similar to P1 and P3 by installing separate 

accessories (see the ICF data sheet).

Surface protection and identification

The external surface is zinc-chromated to 

provide corrosion protection according to 

EN 12284:2003 8.13. 

The Zinc-Chromatization does not cover 

the welding connections. After installation 

has been completed the external surface 

of the valve must be protected against 

corrosion with a suitable top coating.

Coverage of the ID label when painting the 

ICF is recommended.

Precise identification of the ICF is made 

via the ID label on each of the 4 function 

modules. 

Maintenance (fig. 4)

Service

The ICF valve stations are easy to service. 

Do not open the ICF while it is still under 

pressure. 

Upon opening and removal of the 

modules:

-   Check that the flat gaskets and/or 

  O-rings between the module 

  and the housing and O-rings on the  

  function module has not been damaged.

  Replace flat gaskets and O-rings if not  

  intact.  

  A valve with a damaged o-ring/gasket  

  might not  modulate according to the  

 specification.

 

  Flat gaskets and O- are present in the 

  locations shown in fig. 4.

  

CO

2

 applications 

   

When used in CO

2

 systems 

   

the O-rings (see fig. 4) can swell  

  

(grow). 

At service it is recommended to replace 

the actual number of used O-rings before 

the modules are reinstalled in the ICF valve 

body.

Assembly

Remove any dirt from the housing before 

the ICF is assembled. 

-  Check that all channels in the ICF    

  are free of particles or similar debris. 

  If possible, apply some refrigeration oil  

  to ease the insertion of the modules and  

  to protect the O-rings.

Tightening (fig. 5)

Tighten the top covers and plugs with a 

torque wrench, to the values indicated in 

the table (see fig. 5).

Replacing or servicing the function 

module in the ICS, ICM, ICLX and ICSH 

modules:

ICS/ICSH module (fig. 6)

Remove the top cover.

The function module can be lifted out 

using a bolt size M6 or multi-function 

tool screwed into the threaded hole of 

the piston on the function module (fig. 

6). Debris blocking the bolt hole will need 

cleaning.

-   Remove the old module.

-   Oil the O-rings on the new module with  

  a small amount of refrigeration oil.

ICM module (fg. 7)

Remove the existing module (fig. 7):

1. After removing the 4 bolts twist the   

  module approx. 45° in either direction.

2. Push two screwdrivers in between the  

  top cover and the valve body.

3. Pull the screwdrivers upwards to release  

  the function module and its o-rings.

-   Remove the old module.

-  Oil the O-rings on the new module with  

  a small amount of refrigeration oil.

Summary of Contents for ICF 50-4

Page 1: ...ions Orientación todas las configuraciones Orientação todas as configurações Orientacja wszystkie konfiguracje Ориентация все конфигурации 指南 所有配置 ICF 50 4 ICF 65 3 Welding Schweißen Soudure Soldadura Soldagem Spawanie Сварка 焊接 TIG MIG SMAW Gas welding Gasschweißen Soudure au gaz Soldadura con gas Soldagem a gás Spawanie gazowe Газовая сварка 气焊 1a 1b 2 3 ICM ICS ICLX 4 x 90 4 x 90 Danfoss 27L20_...

Page 2: ... Flachdichtung Joint plat Junta plana Junta plana Płaska uszczelka Плоская прокладка 平垫片 Flat gasket Flachdichtung Joint plat Junta plana Junta plana Płaska uszczelka Плоская прокладка 平垫片 Flat gasket Flachdichtung Joint plat Junta plana Junta plana Płaska uszczelka Плоская прокладка 平垫片 Flat gasket Flachdichtung Joint plat Junta plana Junta plana Płaska uszczelka Плоская прокладка 平垫片 Flat gasket...

Page 3: ... ICF 65 3 57 Nm 42 ft lbs 150 Nm 110 6 ft lbs 57 Nm 42 ft lbs ICF 50 4 110 Nm 81 1 ft lbs ICF 65 3 110 Nm 81 1 ft lbs 8a 8b 5 6 7 2 3 3 1 2 2 2 1 1 2 3 3 ICS ICSH ICM ICLX ICF 50 4 60 Nm 44 3 ft lbs ICF 65 3 60 Nm 44 3 ft lbs ICF 50 4 45 Nm 33 2 ft lbs Maintenance Instandhaltung Maintenance Mantenimiento Manutenção Serwis Техническое обслуживание 维护 ...

Page 4: ...5 3 12 SVA S REG SB ICS ICLX ICSH ICM M1 M3 M4 M2 M1 M3 M4 P1 P3 opposite side gegenüberliegende Seite côté opposé lado opuesto lado oposto po przeciwnej stronie противоположная сторона 对侧 P2 P4 opposite side gegenüberliegende Seite côté opposé lado opuesto lado oposto po przeciwnej stronie противоположная сторона 对侧 P2 P4 opposite side gegenüberliegende Seite côté opposé lado opuesto lado oposto ...

Page 5: ...from external loads Use only new gaskets manufactured by Danfoss Ensure that installed valves are properly pressure tested leak tested evacuated before charging with refrigerant in accordance with ANSI IIAR 5 EN378 2 or ISO 5149 2 The enclosed valves must not be mounted in systems where the outlet side of the valve is open to atmosphere The outlet side of the valve must always be connected to the ...

Page 6: ...is present in the cap Then tighten the cap with 16 Nm 12 ft lbs Manual operation of ICLX module fig 10 Normal operation mode For the valve to operate normally under the influence of the pilot valves the spindle of the manual operation device needs to be turned fully clockwise Manual forced opening To manually open the valve the spindle of the manual operation device needs to be turned fully counte...

Page 7: ...gsfrei montiert ist Verwenden Sie nur neue von Danfoss hergestellte Dichtungen Stellen Sie sicher dass die eingebauten Ventile ordnungsgemäß einer Druck und Leckageprüfung unterzogen wurden und vor der Befüllung mit Kältemittel gemäß ANSI IIAR 5 DIN EN 378 2 oder ISO 5149 2 evakuiert wurden Die ICF Ventilstation darf nicht in Anlagen verwendet werden bei denen die Austrittsseite des Ventils zur At...

Page 8: ...ment 2 Zum Deaktivieren der Handbedienung drehen Sie die Handspindel entgegen dem Uhrzeigersinn bis zum oberen Anschlag am Kopfdeckel Um die Rücksitzdichtung zu gewährleisten beenden Sie diesen Schritt mit einem Drehmoment von 8 Nm 5 9 lb ft 3 Befestigen Sie die Kappe wieder und ziehen Sie sie im Uhrzeigersinn mit 8 Nm 5 9 lb ft fest Handbedienung des ICS ICSH Moduls Abb 10 Normaler Betriebsmodus ...

Page 9: ...ie sur laquelle une vanne est installée est correctement soutenue et d équerre par rapport aux sections de raccord Assurez vous que l assemblage final de la vanne est libre de toute contrainte de charges externes Utilisez exclusivement des joints neufs fabriqués par Danfoss Assurez vous que les vannes installées sont soumises à des tests de pression et d étanchéité et sont correctement vidées avan...

Page 10: ...dans le sens des aiguilles d une montre Remarque Faites toujours attention à la tige pendant le fonctionnement en ouverture manuelle 1 Veillez à ce que le circlip atteigne le sommet de l écrou supérieur de la tige manuelle ICSH entretoise entre le circlip et l écrou supérieur de la tige manuelle lors de la rotation de la tige manuelle dans le sens des aiguilles d une montre pour ouvrir la vanne N ...

Page 11: ...icar aceite protector contra el óxido a las superficies interiores Montaje de las válvulas Asegúrese de que las tuberías en las que deba instalarse una válvula se encuentren correctamente apoyadas y sean alineadas totalmente perpendiculares a las secciones de unión Compruebe que las válvulas no soporten tensiones ejercidas por cargas externas una vez finalizada su instalación Use sólo juntas nueva...

Page 12: ... en el sentido de las agujas del reloj hasta el tope Nota Preste siempre atención al vástago durante el uso del mecanismo de apertura manual 1 Compruebe que el anillo de retención alcance el extremo superior del separador entre el anillo de retención y la tuerca superior del vástago manual al girar el vástago manual en el sentido de las agujas del reloj para abrir la válvula No ejerza demasiada fu...

Page 13: ...aisquer tensões causadas por cargas externas Utilize apenas juntas novas fabricadas pela Danfoss Certifique se de que as válvulas instaladas sejam devidamente testadas relativamente a pressão e a vazamentos e que sejam evacuadas antes do carregamento com refrigerante de acordo com ANSI IIAR 5 EN378 2 ou ISO 5149 2 As válvulas não podem ser montadas em sistemas onde o lado de saída da válvula estej...

Page 14: ... base manual ICSH espaçador entre a trava e a porca ao girar no sentido horário para abrir a válvula Nunca utilize torque excessivo e pare de girar quando a trava entrar contato com uma poca espaçador 2 Ao girar a haste no sentido anti horário para desativação da operação manual para o ponto superior aperte o no sentido anti horário com um torque de 8 Nm 5 9 lb ft para o assento posterior 3 Remont...

Page 15: ...wany od razu należy posmarować jego wewnętrzne powierzchnie olejem zabezpieczającym przed korozją Montaż zaworów Należy zwrócić uwagę aby rury do których montowany jest zawór były odpowiednio podparte i ustawione do wykonania właściwego połączenia Sprawdzić czy na zamontowany zawór blokowy nie działają naprężenia wywołane przez obciążenia zewnętrzne Używać wyłącznie nowych uszczelek produkowanych ...

Page 16: ...ię do górnej części górnej nakrętki mechanizmu wrzeciona obsługi ręcznej ICSH dystans pomiędzy zaciskiem C a górną nakrętką mechanizmu wrzeciona obsługi ręcznej podczas wkręcania wrzeciona obsługi ręcznej w prawo w celu otwarcia zaworu Nigdy nie należy stosować nadmiernego momentu Należy przestać obracać gdy zacisk C zetknie się z nakrętką dystansem 2 W celu pełnego otwarcia zaworu ręcznego lub pr...

Page 17: ...вить модули сразу же после сварки и вновь закрыть 2 модуля M1 и M4 чтобы защитить внутреннюю часть клапана до момента готовности системы к работе Если клапан разобран сразу же убедитесь что на внутренние поверхности клапана нанесено масло защищающее его от ржавчины Монтаж клапанов Убедитесь в том что трубопровод в который устанавливается клапан имеет соответствующую опору и установлен перпендикуля...

Page 18: ...трелке для открытия клапана следите за моментом когда стопорное кольцо соприкоснётся с верхом проставки между стопорным кольцом и верхней гайкой ручного штока Категорически запрещается использовать избыточный крутящий момент прекратите вращение когда стопорное кольцо соприкоснётся с проставкой 2 Для деактивации механизма ручного открытия вращайте шток против часовой стрелки до верхней точки затяну...

Page 19: ...终阀体不受外部负载应力影响 只能使用丹佛斯提供的全新垫片 确保安装的阀门在充注制冷剂之前经过 压力测试 泄漏测试和抽空 符合ANSI IIAR 5 EN378 2或ISO 5149 2 系统中ICF组合阀出口不能与大气连通 阀 体出口侧必须连接在系统中或者进行有效 的密封处理 例如用一个焊接 端盖 侧接口连接 图12 ICF阀门具有2组2个单独侧接口 两个较 小接口 P1和 P3可以用于连接检修部件 例如检修阀 仪表或视液镜 两个较大接 口P2和P4可以用于在除霜时 通常为热气 除霜 从蒸发器排液 通过安装单独配件可以使P2和P4转换为类 似于P1和P3的侧接口 参阅ICF技术手册 表面防护和铭牌标识 ICF组合阀已在出厂前进行了镀锌铬处理符 合EN12284 20038 13标准的防腐蚀效果 但不覆盖阀门焊接的连接部分 如果需要 做进一步防腐蚀保护 必须用适当的优质 漆料 对外表面进行抗...

Page 20: ...S ICM ICLX或 ICSH 阀门的安装指南 SVA S或REG SB模块背封 图9 如需对阀门进行背封 应逆时针转动阀杆 直至阀门完全打开 在模块上重新安装阀帽前 请确保阀帽上 存在垫片 然后用16 Nm 12 ft lbs 力矩紧 固阀帽 ICLX模块手动操作 图10 正常工作模式 正常工作模式要让阀门在导阀的控制下正 常工作 须将手动操作装置的旋杆沿顺时 针方向旋转到头 手动强制开启 要手动开启阀门 需要逆时针旋转手动阀 杆 ICS ICSH模块手动操作 图10 正常工作模式 要让阀门在导阀的影响下正常工作 须将 手动操作装置的旋杆沿逆时针方向旋转 手动强制开通 要手动开通阀门 需要顺时针旋转手动操 作装置的旋杆 注 在手动开启工具运行时 始终关注阀杆 1 在顺时针转动手动阀杆开启阀门时 注 意不要过度转动导致阀杆的限位夹与垫 片互相干涉 扭矩切勿过大 且在限位夹接触垫片时 停止...

Reviews: