Installation and application

The maximum tilt angle allowed in GLT80TDC 
compressor (stopped or running) in any of the 
2 below mentioned recommended positions 
is 20º, and maximum tilt angle in the 2 below 
not recommended position is 15º. Apart 
from this specification, below diagrams show 
the recommended and not recommended 
positions while the compressor is running in the 
application.

If compressor has been stopped during a certain 
period of time with an inclination higher than 
15º, it is strongly recommended to not start 
up the compressor immediately after coming 
back to the correct position. We recommend 
waiting at least 30 minutes before starting up the 
compressor.

GLT80TDC compressor is not designed for off-
road mobile applications. If you are interested 

in this type of mobile applications, it has to be 
specifically approved by the manufacturer.

Maximum tilt angle

Off-road applications

RECOMMENDED POSITIONS

β max=20º

NOT RECOMMENDED POSITIONS

α max=15º

Fig 1. Maximum tilt angle 

5

FRCC.PC.041.A1.02

Summary of Contents for GLT80TDC

Page 1: ...Danfoss Light Commercial Refrigeration Compressors GLT80TDC Direct Current 24 42V Mobile Applications Application guidelines http cc danfoss com...

Page 2: ......

Page 3: ...Wiring and Connections 6 The serial port interface 8 Operating voltage 9 Battery protection system 10 Setting up the speed 12 Programming the electronic driver 13 Protections and alarms 14 Compressor...

Page 4: ...ppliance EIM and making the compressor work in slave mode FDC3 electronic driver includes Smart Speed as programming option which is a plug in system for automatically self adapting compressor speed t...

Page 5: ...been stopped during a certain period of time with an inclination higher than 15 it is strongly recommended to not start up the compressor immediately after coming back to the correct position We recom...

Page 6: ...FUSE MUST BE PLACED BETWEEN THE POLE OF THE BATTERY OR DC POWER SUPPLY AND THE POWER INPUT TERMINAL OF THE ELECTRONIC DRIVER 12V SYSTEMS 30A FUSE 24V SYSTEMS 30A FUSE 42V SYSTEMS 20A FUSE In some spe...

Page 7: ...iagram Fig 2 FDC3 wiring scheme Fig 3 Connection of FDC3 driver to the compressor The FDC3 electronic driver features a terminal board where all connections are made The terminal lay out is described...

Page 8: ...y alarm Set up either the compressor speed or the battery protection level through physical connections between IN1 IN2 and COM Connect the electronic driver as slave to an Electronic Integral Manager...

Page 9: ...is within 33 and 42 4V Special programming option The compressor can be powered by a variable DC source as for instance a photovoltaic panel in which the output voltage strongly depends on the intens...

Page 10: ...0 40 0 2 0 3 0 Special 9 0 40 0 1 0 3 0 Externally using COM IN1 and IN2 of SPI This option prevents from the possibility of setting up the speed externally using COM IN1 and IN2 of SPI as defined in...

Page 11: ...than the maximum nominal voltage 14V 28V and 42V for 12V 24V and 42V systems respectively A linear function of the battery voltage in the range between the cut in and the maximum nominal voltages This...

Page 12: ...Sleep Energy Saving is done in the same way as Sleep Slave mode Under this mode variable speed is controlled by an Electronic Integral Manager of the appliance EIM permanently connected to the electro...

Page 13: ...incompatible with external battery protection step 8 2 7 2 Smart Speed mode Select maximum fixed speed or external switcher connected to SPI and proceed as described in 7 1 1 or 7 1 2 respectively 7 3...

Page 14: ...om the power supply The intervention of the thermostat during the sequence of automatic restart attempts interrupts and resets the sequence The SPI can be configured in a way that a LED can be connect...

Page 15: ...rd ON OFF according with CECOMAF GT 4004 standard Vibrations according with ASTM 5728 Level I standard Application Application MBP HBP A C Refrigerant R134a Evaporation temp range C 25 to 10 Expansion...

Page 16: ...Compressor overload Electronic driver overheat Programmable running modes Standard Smart Speed Sleep Sleep Energy Saving Slave Setup by default Running mode Standard Speed selection external switcher...

Page 17: ...P 2 000 116 1 15 264 1 64 577 2 34 2 500 142 1 13 330 1 62 712 2 26 3 000 168 1 11 395 1 58 842 2 17 3 500 192 1 09 454 1 54 968 2 07 r p m T evap 25 C T evap 10 C T evap 7 2 C Pe W I A Pe W I A Pe W...

Page 18: ......

Page 19: ......

Page 20: ...technology specialists Today we operate from engineering and manufacturing facilities spanning across three continents FRCC PC 041 A1 02 Danfoss Light Commercial Refrigeration Compressors made by Hua...

Reviews: