FC 300 CANopen
54
MG.33.J1.02 VER. 050301 – VLT is a registered Danfoss trademark
No Communication with the Drive
If there is no communication with the drive,
proceed with the following checks:
Check 1: Is the cabling correct?
Check that the cables are connected to the
correct terminals as shown in the diagram.
Pin
no.
Terminal
Colour Name
1 - -
Reserved
2 CAN_L
Blue CAN
LOW
3 Drain
(bare) Screen
4 CAN_H
White CAN
HIGH
5 - -
Reserved
Check 2: Is the correct EDS file installed?
Download the correct EDS file from http://www.danfoss.com/drives.
Check 3: Is the bus connection terminated at both ends?
If not, terminate the bus connection with termination resistors at the initial and final nodes, as shown
in the following diagram.
Termination is performed between terminal 2 (CAN_L) and 4 (CAN_H) with
a resistor: 121 Ohm, 1% metal film, ¼ Watt.