EKC 361 

Manual  RS8AE802  ©  Danfoss  12-2009 

9

Data

Ordering

Type

Function

Code No.

EKC 361

Evaporating pressure controller

084B7060

EKA 174

Data communication module

 (accessories), (RS 485 module)

with galvanic separation

084B7124

Necessary connections

Terminals:

25-26  Supply voltage 24 V a.c.
17-18  Signal from actuator (from NTC)
23-24  Supply to actuator (to PTC)
20-21  Pt 1000 sensor at evaporator outlet
1-2 

Switch function for start/stop of regulation. If a switch is 
not connected, terminals 1 and 2 must be shortcircuited.

Application dependent connections

Terminal:

12-13   Alarm relay

There is connection between 12 and 13 in alarm situa tions 
and when the controller is dead

8-10 

Relay switch for start/stop of fan

9-10 

Relay switch for start/stop of solenoid valves

18-19  Current signal from other regulation (Ext.Ref.)
21-22  Pt 1000 sensor for monitoring
2-5 

Current output for Sair/Saux temperature or ICAD actuator  

 

for ICM valve

3-4  

Data communication

 

Mount only, if a data communication module has been 

mounted.

It is 

important that the installation of the data communi-

cation cable be done correctly. Cf. separate literature No. 

RC8AC..

Connections

Supply voltage

24 V a.c. +/-15% 50/60 Hz, 80 VA
(the supply voltage is galvanically separated 

from the input and output signals)

Power consumption

Controller
Actuator

5 VA
75 VA

Input signal 

Current signal

4-20 mA or 0-20 mA

Digital input from external contact function

Sensor input

2 pcs. Pt 1000 ohm

Output signal

Current signal

4-20 mA or 0-20 mA
Max. load: 200 ohm

Relay output

2 pcs. SPST

AC-1: 4 A (ohmic)
AC-15: 3 A (inductive)

Alarm relay

1 pcs. SPST

Actuator

Input

Temperature signal from 
sensor in the  actuator

Output

Pulsating 24 V a.c. to 

actuator

Data communication

Possible to connect a data communication 

module

Ambient 
temperature

During operation
During transport

-10 - 55°C
-40 - 70°C

Enclosure

IP 20

Weight

300 g

Mounting

DIN rail

Display

LED, 3 digits

Terminals

max. 2.5 mm

2

 multicore

Approvals

EU Low Voltage Directive and EMC demands re 
CE-marking complied with.
LVD-tested acc. to EN 60730-1 and EN 60730-

2-9

EMC-tested acc. to EN50081-1 and EN 50082-2

Temperature sensor Pt 1000 ohm:

 ..........

Kindly refer to catalogue RK0YG...

Valves:

 .............................................................

DKRCI.PD.HT0.A

Data communication

Wire length: See appendix 2

CVQ/
CVMQ/
KVQ

Summary of Contents for EKC 361

Page 1: ...REFRIGERATION AND AIR CONDITIONING Controller for regulation of media temperature EKC 361 Manual...

Page 2: ...pt high and waste is limited A transient phenomenon can be controlled with the adaptive function Select either Fast build up where underswings are allowed Not quite so fast build up where underswings...

Page 3: ...r ICS PM and ICM The EKC 361 can also operate a solenoid valve in the liquid line Digital output on terminal 9 and 10 It will follow the status of Digital Input however if a low temperature alarm is d...

Page 4: ...hecks the temperature pres sure in the actuator s pressure vessel In this way a very stable control system is obtained If there is a deviation between the required and the registered temperature the c...

Page 5: ...an also be accomplished with the external switch function See also appendix 1 r12 Main Switch Alarm The controller can give alarm in different situations When there is an alarm all the light emitting...

Page 6: ...nd to the setting in o27 Sair Saux max value 20 mA will correspond to the setting in o28 If ICM has been selected n03 6 OD u24 to control ICM is send out to the analog output o27 and o28 is not active...

Page 7: ...ssolution wil be better than 0 2 C o28 Temp at AO max Service A number of controller values can be printed for use in a service situation Read the temperature at the Sair sensor calibrated value u01 A...

Page 8: ...splay Shows the temperature at the selected sensor At ICM valve OD also can be selected C Reference Set the required room temperature 70 C 160 C 10 C Temperature unit r05 C F C Input signal s temperat...

Page 9: ...rtant that the installation of the data communi cation cable be done correctly Cf separate literature No RC8AC Connections Supply voltage 24 V a c 15 50 60 Hz 80 VA the supply voltage is galvanically...

Page 10: ...ogramme will for exam ple upload all the collected tempera ture values once a day Measurements are shown at one side and settings at the other You will also be able to see the parameter names of the f...

Page 11: ...ion pressure will have a belonging to value which in turn indicates the value of the n02 setting Due to tolerances in the actuator the setting value must be 10 K lower than shown in the curve CVQ KVQ...

Page 12: ...V a c 10 15 under all working conditions If voltage drops under some working conditions the transformer is undersized Loss of charge in actuator Replace actuator Media temperature too high Actuator fe...

Page 13: ...alues where the valve is exactly in mesh the valve will all the time remain active in its regulation If the actuator is replaced at a later date this procedure must be repeated for the new actuator Mi...

Page 14: ...14 Manual RS8AE802 Danfoss 12 2009 EKC 361...

Page 15: ...EKC 361 Manual RS8AE802 Danfoss 12 2009 15...

Page 16: ...right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications a...

Reviews: