Manual  RS8AE802  ©  Danfoss  12-2009 

EKC 361

Actuator type

Here you define the actuator mounted in the system:
1: CVQ -1-5 bar
2: CVQ 0-6 bar
3: CVQ 1.7-8 bar
4: CVMQ
5: KVQ
6: ICM

n03

Valve type

P: Amplification factor Kp

If the Kp value is reduced the regulation becomes slower.

n04

Kp factor

I: Integration time Tn

The I-setting can be cancelled by setting the value to max. (600s). If it is set to 600s, parameter 
n07 must be set to “0”. (If the Tn value is increased the regulation becomes slower).

n05

Tn sec.

D: Differentiation time Td

The D-setting can be cancelled by setting the value to min. (0).

n06

Td sec.

Transient phenomenon

If the refrigeration requires a very fast transient phenomenon or must not have an underswing or 
temperature shift, this function can be used.  (see page 4)
0: Ordinary regulating technique

1: Fast building-up where a minor underswing is allowed

2: Not quite so fast building-up, but without underswing

n07

Q-ctrl. mode

OD - Opening degree Max. Limitation - ICM only

When ICM has been selected (n03=6) the Maximum OD can be entered. ICM will never go above 
this value. (If n32=n33, ICM is forced to this value)

n32

ICM OD Max.

OD - Opening degree Min. Limitation - ICM only

When ICM has been selected (n03=6) the Minimum OD can be entered. ICM will never go below 
this value. (If n32=n33, ICM is forced to this value)

n33

ICM OD Min.

Miscellaneous
Output signal

The controller can transmit a current signal via the analog output (terminal 2 and 5). Range of 

current signal can be selected below:

If (017=Air) Sair will send out to the analog output.
If (017=Au) Saux will send out to the analog output

S

air

/S

aux

 min. value (0 or 4 mA) will correspond to the setting in "o27"

S

air

/S

aux

 max. value (20 mA) will correspond to the setting in "o28"

If ICM has been selected (n03=6)
 OD (u24) to control ICM, is send out to the analog output
 (o27) and (o28) is not active

Range for current signal:
0: No output signal

1: 4-20 mA

2: 0-20 mA

o09

AO type

Input signal

If you wish to connect a signal that is to displace the controller’s control reference, the signal 
must be defined in this menu.

0: No signal

1: 4-20 mA

2: 0-20 mA

(4 or 0 mA will not give a displacement. 20 mA will displace the reference by the value set in 

menu r06).

o10

AI type

Data communication

If the controller is built into a network with data communication, it must have an address, and 
the master gateway of the data communication must then know this address.
These settings can only be made when a data communication module has been mounted in the 

controller and the installation of the data communication cable has been completed.
This installation is mentioned in a separate document “RC8AC”.

Following installation of a data communica-

tion module, the controller can be operated 
on a par with the other controllers in ADAP-
KOOL® refrigeration controls.

The address is set between 1 and 60

o03

-

The address is sent to the gateway when the menu is set in pos. ON
(The setting will automatically change back to Off after a few seconds.)

o04

-

Language

This setting is only required if data communication is connected to the controller.
Settings: 0=English, 1=German, 2=French, 3=Danish, 4=Spanish and 6=Swedish
When the controller is operated via data communication, the texts in the right-hand column will 

be shown in the selected language.

When you change the setting to an other language you must activate o04 before "the new 
language" can be visible from the AKM program.

o11

Language 

Frequency

Set the net frequency.

o12

50 / 60 Hz
(50=0, 60=1)

Summary of Contents for EKC 361

Page 1: ...REFRIGERATION AND AIR CONDITIONING Controller for regulation of media temperature EKC 361 Manual...

Page 2: ...pt high and waste is limited A transient phenomenon can be controlled with the adaptive function Select either Fast build up where underswings are allowed Not quite so fast build up where underswings...

Page 3: ...r ICS PM and ICM The EKC 361 can also operate a solenoid valve in the liquid line Digital output on terminal 9 and 10 It will follow the status of Digital Input however if a low temperature alarm is d...

Page 4: ...hecks the temperature pres sure in the actuator s pressure vessel In this way a very stable control system is obtained If there is a deviation between the required and the registered temperature the c...

Page 5: ...an also be accomplished with the external switch function See also appendix 1 r12 Main Switch Alarm The controller can give alarm in different situations When there is an alarm all the light emitting...

Page 6: ...nd to the setting in o27 Sair Saux max value 20 mA will correspond to the setting in o28 If ICM has been selected n03 6 OD u24 to control ICM is send out to the analog output o27 and o28 is not active...

Page 7: ...ssolution wil be better than 0 2 C o28 Temp at AO max Service A number of controller values can be printed for use in a service situation Read the temperature at the Sair sensor calibrated value u01 A...

Page 8: ...splay Shows the temperature at the selected sensor At ICM valve OD also can be selected C Reference Set the required room temperature 70 C 160 C 10 C Temperature unit r05 C F C Input signal s temperat...

Page 9: ...rtant that the installation of the data communi cation cable be done correctly Cf separate literature No RC8AC Connections Supply voltage 24 V a c 15 50 60 Hz 80 VA the supply voltage is galvanically...

Page 10: ...ogramme will for exam ple upload all the collected tempera ture values once a day Measurements are shown at one side and settings at the other You will also be able to see the parameter names of the f...

Page 11: ...ion pressure will have a belonging to value which in turn indicates the value of the n02 setting Due to tolerances in the actuator the setting value must be 10 K lower than shown in the curve CVQ KVQ...

Page 12: ...V a c 10 15 under all working conditions If voltage drops under some working conditions the transformer is undersized Loss of charge in actuator Replace actuator Media temperature too high Actuator fe...

Page 13: ...alues where the valve is exactly in mesh the valve will all the time remain active in its regulation If the actuator is replaced at a later date this procedure must be repeated for the new actuator Mi...

Page 14: ...14 Manual RS8AE802 Danfoss 12 2009 EKC 361...

Page 15: ...EKC 361 Manual RS8AE802 Danfoss 12 2009 15...

Page 16: ...right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications a...

Reviews: