Manual  RS8AE802  ©  Danfoss  12-2009 

EKC 361

Function

Very accurate temperature control

With this system where controller, pilot valve and main valve have 
been adapted for optimum use in the refrigerating plant, the re

-

frigerated products may be stored with temperature fluctuations 
of less than ±0.25°C.

High air humidity

As the evaporating temperature is constantly adapted to the 
refrigeration needs and will always be as high as possible with a 
very small temperature fluctuation, the relative air humidity in the 
room will be kept at a maximum.
Drying-out of the products will in this way be reduced to a mini

-

mum.

Temperature is quickly attained

With the built-in PID control and the possibility of choosing be

-

tween three transient phenomena, the controller can be adapted 
to a kind of temperature performance that is optimum for this 
particular refrigerating plant. See parameter (n07).
• 

Fastest

 possible cooling

• Cooling with 

less

 underswing

• Cooling where underswing is 

unwanted.

Regulation ICS/PM with CVQ

The controller receives signals from room sensor S

air

. This room 

sensor must be placed at the air outlet from the evaporator to 
obtain the best possible regulation. The controller sees to it that 
the required room temperature is maintained.
Built-in between the controller and the actuator is a so-called 

inner control loop which constantly checks the temperature (pres

-

sure) in the actuator’s pressure vessel. In this way a very stable 
control system is obtained.
If there is a deviation between the required and the registered 
temperature the controller will immediately send more or fewer 

pulses to the actuator to counteract the error. A change of the 
number of pulses will act on the temperature and hence the 
pressure in the pressure vessel. As the charging pressure and the 
evaporating pressure p

0

 follow each other, a changed charging 

pressure will produce the effect that the valve’s opening degree is 

also changed. The ICS/PM with CVQ system maintains the pressure 
in the evaporator whatever pressure changes there may be on the 
suction side (on the ICS/PM valve’s outlet).

Evaporating pressure limitation (p

0

 limitation)

The inner control loop mentioned above also causes the evapora-

ting pressure to stay within a fixed limit. In this way the system is 
safeguarded against a too low supply air temperature.
It offers the following advantages:
- High-temperature systems can be connected to low-tempera ture 

compressor units

- Protection against icing on evaporator

- Frost protection of liquid coolers

Regulation with ICM

When using ICM as selected valve the system will still control ICM 

in order to maintain S

air

 according to entered setpoint.

This system does not inlude any inner control loop.
It is a direct operating and pressure independent valve for control

-

ling media temperatur. (S

air

).

The allowed temperature in the actuator determines the evapora ting pressure

Actuator temperature

Summary of Contents for EKC 361

Page 1: ...REFRIGERATION AND AIR CONDITIONING Controller for regulation of media temperature EKC 361 Manual...

Page 2: ...pt high and waste is limited A transient phenomenon can be controlled with the adaptive function Select either Fast build up where underswings are allowed Not quite so fast build up where underswings...

Page 3: ...r ICS PM and ICM The EKC 361 can also operate a solenoid valve in the liquid line Digital output on terminal 9 and 10 It will follow the status of Digital Input however if a low temperature alarm is d...

Page 4: ...hecks the temperature pres sure in the actuator s pressure vessel In this way a very stable control system is obtained If there is a deviation between the required and the registered temperature the c...

Page 5: ...an also be accomplished with the external switch function See also appendix 1 r12 Main Switch Alarm The controller can give alarm in different situations When there is an alarm all the light emitting...

Page 6: ...nd to the setting in o27 Sair Saux max value 20 mA will correspond to the setting in o28 If ICM has been selected n03 6 OD u24 to control ICM is send out to the analog output o27 and o28 is not active...

Page 7: ...ssolution wil be better than 0 2 C o28 Temp at AO max Service A number of controller values can be printed for use in a service situation Read the temperature at the Sair sensor calibrated value u01 A...

Page 8: ...splay Shows the temperature at the selected sensor At ICM valve OD also can be selected C Reference Set the required room temperature 70 C 160 C 10 C Temperature unit r05 C F C Input signal s temperat...

Page 9: ...rtant that the installation of the data communi cation cable be done correctly Cf separate literature No RC8AC Connections Supply voltage 24 V a c 15 50 60 Hz 80 VA the supply voltage is galvanically...

Page 10: ...ogramme will for exam ple upload all the collected tempera ture values once a day Measurements are shown at one side and settings at the other You will also be able to see the parameter names of the f...

Page 11: ...ion pressure will have a belonging to value which in turn indicates the value of the n02 setting Due to tolerances in the actuator the setting value must be 10 K lower than shown in the curve CVQ KVQ...

Page 12: ...V a c 10 15 under all working conditions If voltage drops under some working conditions the transformer is undersized Loss of charge in actuator Replace actuator Media temperature too high Actuator fe...

Page 13: ...alues where the valve is exactly in mesh the valve will all the time remain active in its regulation If the actuator is replaced at a later date this procedure must be repeated for the new actuator Mi...

Page 14: ...14 Manual RS8AE802 Danfoss 12 2009 EKC 361...

Page 15: ...EKC 361 Manual RS8AE802 Danfoss 12 2009 15...

Page 16: ...right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications a...

Reviews: