Manual  RS8AE802  ©  Danfoss  12-2009 

EKC 361

Start of controller

When the electric wires have been connected to the controller, 

the following points have to be attended to before the regulation 
starts:

1. Switch off the external ON/OFF switch that starts and stops the 

regulation.

2. Follow the menu survey on page 7, and set the various para-

  meters to the required values.

3. Switch on the external ON/OFF switch, and regulation will start.

If the temperature fluctuates

When the refrigerating system has been made to work steadily, 
the controller’s factory-set control parameters should in most 
cases provide a stable and relatively fast regulating system.
If the system on the other hand oscillates, you must register the 

periods of oscillation and compare them with the set integration 
time T

n

, and then make a couple of adjustments in the indicated 

parameters.

Symptom

Defect

Confirmation of defect

Media temperature too low.
Actuator feels cold.

Short-circuited NTC resistor in 
actuator.

If less than 100 ohm is measured across terminals 17 and 18 (disassemble the lead), 
the NTC or the leads are short-circuited. Check the leads.

Defective PTC resistor  (heating 

element) in actuator.

If more than 30 ohm or 0 ohm is measured across terminal 23 and 24 (disassemble 
the lead), either the PTC or the leads are defective.
Check the leads.

Media temperature too low.
Actuator fells warm.

Undersized cable to CVQ.

Measure voltage across terminanls 77 and 78  (min. 18 V a.c.).
Measure resistance in power cables to CVQ (max. 2 ohm)

Undersized 24 V transformer.

Measue voltage across transformer output terminals (24 V a.c. +10/ -15%) under all 
working conditions.
If voltage drops under some working conditions the transformer is undersized.

Loss of charge in actuator.

Replace actuator.

Media temperature too high. 
Actuator feels cold.

Fault in refrigerant plant.

Examine platn for ther defects.

Media temperature too high. 
Actuator feels warm.

Cut out NTC resistor in actuator.

If more than 200 kohm is measured across terminals 17 and 18 (disassemble the 
lead), either the NTC or leads are disconnected. 
Check the leads.

Trouble shooting - ICS/PM with CVQ

In addition to the error messages transmitted by the controller, 
the table below may help identifying errors and defects.

If the time of oscillation is longer than the integration time:

(T

p

 > T

n

 , (T

n

 is, say, 4 minutes))

1. Increase T

n

 to 1.2 times T

p

2. Wait until the system is in balance again
3. If there is still oscillation, reduce K

p

 by, say, 20%

4. Wait until the system is in balance
5. If it continues to oscillate, repeat 3 and 4

If the time of oscillation is shorter than the integration time:

(T

p

 < T

n

 , (T

n

 is, say, 4 minutes))

1. Reduce K

p

 by, say, 20% of the scale reading

2. Wait until the system is in balance
3. If it continues to oscillate, repeat 1 and 2

4. If the system has been fitted with a thermostatic expansion 

valve, it must be set to minimum stable superheating. (If a 
specific T0 is required for the adjustment of the ex pansion valve, 
the two setting values for the actuator temperature (n01 and 

n02) can be set to the belonging value while the adjustment 

of the expansion valve is carried out. Remember to reset the 

values).

5. Follow the actual room temperature on the display. (On 

terminals 2 and 5 a current signal can be transmitted which 

represents the room temperature. Connect a data collection 

unit, if applicable, so that the temperature performance can be 

followed).

Summary of Contents for EKC 361

Page 1: ...REFRIGERATION AND AIR CONDITIONING Controller for regulation of media temperature EKC 361 Manual...

Page 2: ...pt high and waste is limited A transient phenomenon can be controlled with the adaptive function Select either Fast build up where underswings are allowed Not quite so fast build up where underswings...

Page 3: ...r ICS PM and ICM The EKC 361 can also operate a solenoid valve in the liquid line Digital output on terminal 9 and 10 It will follow the status of Digital Input however if a low temperature alarm is d...

Page 4: ...hecks the temperature pres sure in the actuator s pressure vessel In this way a very stable control system is obtained If there is a deviation between the required and the registered temperature the c...

Page 5: ...an also be accomplished with the external switch function See also appendix 1 r12 Main Switch Alarm The controller can give alarm in different situations When there is an alarm all the light emitting...

Page 6: ...nd to the setting in o27 Sair Saux max value 20 mA will correspond to the setting in o28 If ICM has been selected n03 6 OD u24 to control ICM is send out to the analog output o27 and o28 is not active...

Page 7: ...ssolution wil be better than 0 2 C o28 Temp at AO max Service A number of controller values can be printed for use in a service situation Read the temperature at the Sair sensor calibrated value u01 A...

Page 8: ...splay Shows the temperature at the selected sensor At ICM valve OD also can be selected C Reference Set the required room temperature 70 C 160 C 10 C Temperature unit r05 C F C Input signal s temperat...

Page 9: ...rtant that the installation of the data communi cation cable be done correctly Cf separate literature No RC8AC Connections Supply voltage 24 V a c 15 50 60 Hz 80 VA the supply voltage is galvanically...

Page 10: ...ogramme will for exam ple upload all the collected tempera ture values once a day Measurements are shown at one side and settings at the other You will also be able to see the parameter names of the f...

Page 11: ...ion pressure will have a belonging to value which in turn indicates the value of the n02 setting Due to tolerances in the actuator the setting value must be 10 K lower than shown in the curve CVQ KVQ...

Page 12: ...V a c 10 15 under all working conditions If voltage drops under some working conditions the transformer is undersized Loss of charge in actuator Replace actuator Media temperature too high Actuator fe...

Page 13: ...alues where the valve is exactly in mesh the valve will all the time remain active in its regulation If the actuator is replaced at a later date this procedure must be repeated for the new actuator Mi...

Page 14: ...14 Manual RS8AE802 Danfoss 12 2009 EKC 361...

Page 15: ...EKC 361 Manual RS8AE802 Danfoss 12 2009 15...

Page 16: ...right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications a...

Reviews: