EKC 361
Manual RS8AE802 © Danfoss 12-2009
11
Appendix 1
Interaction between internal and external start/stop functions
and active functions.
Connection between the evaporating temperature and the
actuator’s temperature (the values are approximate).
n01: The highest regulated room temperature will have a be longing t
o
value which
in turn indicates the value of the n01 setting. Due to tolerances in the actua-
tor, the setting value must be 10 K
higher
than shown in the curve.
n02: The lowest occurring suction pressure will have a belonging t
o
value which in
turn indicates the value of the n02 setting. Due to tolerances in the actuator,
the setting value must be 10 K
lower
than shown in the curve.
CVQ
KVQ
CVMQ
Appendix 2
Cable length for the
CVQ
actuator
The actuator must be supplied with 24 V a.c. ± 10%.
To avoid excessive voltage loss in the cable to the actuator, use a
thicker cable for large distances.
Wire cross section
Cable length
Internal Start/stop
Off
Off
On
On
External Start/stop
Off
On
Off
On
Refrigeration
Off
On
Actuator
Stand-by
Regulating
Actuator temperature
"n02"
"n02" to "n01"
Fan relay
Off
On
Expansion valve relay
Off
On
Temperature monitoring
No
Yes
Sensor monitoring
Yes
Yes
Appendix 3