EKC 361 

Manual  RS8AE802  ©  Danfoss  12-2009 

5

Survey of functions

Function

Para- 

meter

Parameter by operation via data com-
munication

Normal display

Normally S

air

 (017=Air) will be shown as running display value. If lower button is activated

S

aux

 will be displayed for 5 sec, and then return to S

air

If (017=Au) Saux will be shown as running display value. If lower button is activated
Sair will be displayed for 5 sec, and then return to Saux

If ICM has been selected (n03=6)
If (017=Air) S

air

 (017=Air) will be shown as running display value. If lower button is activated OD 

(u24) will be displayed for 5 sec, and then return to S

air

.

If (017=Au) OD (u24) will be shown as running display value. If lower button is activated S

air

 will 

be displayed for 5 sec, and then return to OD (u24)

Air temp.

Reference
Setpoint

Regulation is performed based on the set value provided that there is no external contribution 
(o10).
(Push both buttons simultaneously to set the setpoint).

-

SP Temp.

Temperature unit

Here you select whether the controller is to indicate the temperature values in °C or in °F. If  indi

-

cation in °F is selected, other temperature settings will also change over to Fahrenheit, either as 

absolute values or as delta values.

r05

Temp unit

°C=0, 
°F=1
(In AKM only °C is displayed whatever the 

setting)

External contribution to the setpoint

This setting determines how large a contribution (in °C/°F) is to be added to the set setpoint 
when the input signal is max. (20 mA).

r06

Ext. Ref.off set (°C/°F)

Correction of signal from S

air

(Compensation possibility through long sensor cable).

r09

Adjust S

Air

  (°C/°F)

Correction of signal from S

aux

(Compensation possibility through long sensor cable).

r10

Adjust S

Aux

  (°C/°F)

Start/stop of refrigeration

With this setting refrigeration can be started and stopped. Start/stop of refrigeration can also be 
accomplished with the external switch function. See also appendix 1.

r12

Main Switch

Alarm

The controller can give alarm in different situations. When there is an alarm all the light-emitting 
diodes (LED) will flash on the controller front panel, and the alarm relay will cut in.

Alarm for upper deviation

The alarm for too high S

air

 temperature is set here. The value is set in Kelvin. The alarm becomes 

active when the S

air

 temperature exceeds the actual reference plus A01. (The actual reference (SP 

+ r06) can be seen in u02).

A01

Upper deviation

Alarm for lower deviation

The alarm for too low S

air

 temperature is set here. The value is set in Kelvin. The alarm becomes 

active when the S

air

 temperature drops below the actual reference minus A02. If a low tempera

-

ture alarm is detected (A2 alarm) the solenoid valve in the liquid line (Digital output on terminal 

9 and 10) will be closed

A02

Lower deviation

Alarm delay

If one of the two limit values is exceeded, a timer function will commence. The alarm will not 
become active until the set time delay has been passed. The time delay is set in minutes.

A03

Temp alarm delay

With data communication the importance 
of the individual alarms can be defined. 

Setting is carried out in the “Alarm destina-
tions” menu. See also page 10.

Control parameters
Actuator’s max. temperature

Set the temperature (°C) the actuator is to have at the limit of the regulating range. The setting 
ensures that the actuator will not become superheated and work itself away from the regulating 

range. Due to tolerances in the actuator the value must be set 10K higher than indicated in the 
curves on page 11.

n01

Q-max. temp.

Actuator’s min. temperature

Set the temperature (°C) the actuator will have at the limit of the regulating range. The setting 
ensures that the actuator will not become too cold and work itself away from the regulating 

range. Due to tolerances in the actuator the value must be set 10K lower than indicated in the 
curves on page 11.

n02

Q-min. temp.

Summary of Contents for EKC 361

Page 1: ...REFRIGERATION AND AIR CONDITIONING Controller for regulation of media temperature EKC 361 Manual...

Page 2: ...pt high and waste is limited A transient phenomenon can be controlled with the adaptive function Select either Fast build up where underswings are allowed Not quite so fast build up where underswings...

Page 3: ...r ICS PM and ICM The EKC 361 can also operate a solenoid valve in the liquid line Digital output on terminal 9 and 10 It will follow the status of Digital Input however if a low temperature alarm is d...

Page 4: ...hecks the temperature pres sure in the actuator s pressure vessel In this way a very stable control system is obtained If there is a deviation between the required and the registered temperature the c...

Page 5: ...an also be accomplished with the external switch function See also appendix 1 r12 Main Switch Alarm The controller can give alarm in different situations When there is an alarm all the light emitting...

Page 6: ...nd to the setting in o27 Sair Saux max value 20 mA will correspond to the setting in o28 If ICM has been selected n03 6 OD u24 to control ICM is send out to the analog output o27 and o28 is not active...

Page 7: ...ssolution wil be better than 0 2 C o28 Temp at AO max Service A number of controller values can be printed for use in a service situation Read the temperature at the Sair sensor calibrated value u01 A...

Page 8: ...splay Shows the temperature at the selected sensor At ICM valve OD also can be selected C Reference Set the required room temperature 70 C 160 C 10 C Temperature unit r05 C F C Input signal s temperat...

Page 9: ...rtant that the installation of the data communi cation cable be done correctly Cf separate literature No RC8AC Connections Supply voltage 24 V a c 15 50 60 Hz 80 VA the supply voltage is galvanically...

Page 10: ...ogramme will for exam ple upload all the collected tempera ture values once a day Measurements are shown at one side and settings at the other You will also be able to see the parameter names of the f...

Page 11: ...ion pressure will have a belonging to value which in turn indicates the value of the n02 setting Due to tolerances in the actuator the setting value must be 10 K lower than shown in the curve CVQ KVQ...

Page 12: ...V a c 10 15 under all working conditions If voltage drops under some working conditions the transformer is undersized Loss of charge in actuator Replace actuator Media temperature too high Actuator fe...

Page 13: ...alues where the valve is exactly in mesh the valve will all the time remain active in its regulation If the actuator is replaced at a later date this procedure must be repeated for the new actuator Mi...

Page 14: ...14 Manual RS8AE802 Danfoss 12 2009 EKC 361...

Page 15: ...EKC 361 Manual RS8AE802 Danfoss 12 2009 15...