Installation, operation and maintenance instructions - VMGFE102

12  NOMINAL SYSTEM WATER FLOW CONTROL

The water circulation pumps of the AR05 units have been 
sized to allow the hydronic modules to cover all possible 
confi gurations based on the specifi c installation conditions, 
i.e. for various temperature diff erences between the entering 
and the leaving water (∆T) at full load, which can vary 
between 3 and 10 K. 

This required diff erence between the entering and leaving 
water temperature determines the nominal system fl ow rate. 
Use this specifi cation for the unit selection to fi nd the system 
operating conditions. 

In particular, collect the data to be used for the control of the 
system fl ow rate:
• 

Unit without a hydronic module: nominal unit pressure 
drop (plate heat exc internal piping),

• 

Unit with fi xed-speed pump: nominal fl ow rate,

• 

Unit with variable-speed pump, controlled by a diff e-
rence in constant pressure between the unit inlet and 
outlet: nominal fl ow rate,

• 

Unit with variable-speed pump, controlled by the heat 
exchanger temperature diff erence: nominal temperature 
diff erence at the heat exchanger.

If this information is not available at the system start-up, 
contact the technical service department responsible for the 
installation to get it.

These characteristics can be obtained from the technical 
literature using the unit performance tables for a ∆T of 5 K at 
the water heat exchanger or with the Electronic Catalogue 
selection program for all ∆T conditions other than 5 K in the 
range of 3 to 10 K.

12.1 - Units without hydronic module

The nominal system fl ow rate is controlled by a manual valve 
that must be on the water leaving piping of the system (item 
20 in the typical hydronic circuit diagram). 

Due to the pressure drop it generates in the hydronic system 
this fl ow control valve permits adjustment of the pressure/
system fl ow rate curve in accordance with the pump pressure/
fl ow rate curve to obtain the nominal fl ow rate at the required 
operating point (see example for unit size AR05 078).

The pressure drop reading in the unit (plate heat exc 
internal piping) is used as means of control.

This reading can be taken with pressure gauges that must be 
installed at the unit inlet and outlet (item 19).

As the total system pressure drop is not known exactly at the 
start-up, the water fl ow rate must be adjusted with the 
control valve to obtain the specifi c fl ow rate for this system.

Hydronic circuit cleaning procedure

• 

Open the valve fully (item 20).

• 

Start-up the system pump.

• 

Read the plate heat exchanger pressure drop by taking 
the diff erence of the readings of the pressure gauge 
connected to the unit inlet and outlet (item 19).

• 

Let the pump run for two consecutive hours to clean the 
hydronic circuit of the system (presence of solid 
contaminants).

• 

Take another reading.

• 

Compare this value to the initial value.

• 

If the pressure drop has decreased, this indicates that 
the screen fi lter must be removed and cleaned, as the 
hydronic circuit contains solid particles. In this case close 
the shut-off  valves at the water inlet and outlet (item 17) 
and remove the screen fi lter (item 18) after emptying 
the hydronic section of the unit (item 6).

• 

Purge the air from the circuit (items 5 and 15).

• 

Renew, if necessary, to ensure that the fi lter is not 
contaminated.

Water fl ow control procedure

When the circuit is cleaned, read the pressures at the 
pressure gauges (entering water pressure - leaving water 
pressure), to fi nd out the unit pressure drop (plate heat 
exc internal water piping).

Compare the value obtained with the theoretical selection 
value. If the pressure drop measured is higher than the value 
specifi ed this means that the unit fl ow rate (and thus system 
fl ow rate) is too high. The pump supplies an excessive fl ow rate 
based on the global pressure drop of the application. In this case 
close the control valve and read the new pressure diff erence. 

Proceed by successively closing the control valve until you 
obtain the specifi c pressure drop that corresponds to the 
nominal fl ow rate at the required unit operating point.

NOTE: If the system has an excessive pressure drop in 
relation to the available static pressure provided by the 
system pump the nominal water fl ow rate cannot be 
obtained (the resulting fl ow rate is lower) and the tempe-
rature diff erence between the water heat exchanger entering 
and leaving water will increase.

To reduce the pressure drops of the hydronic system, it is 
necessary:
• 

to reduce the individual pressure drops as much as 
possible (bends, level changes, accessories, etc.).

• 

to use a correctly sized piping diameter.

• 

to avoid hydronic system extensions, wherever possible.

Summary of Contents for AR05 017 Series

Page 1: ...t Pumps Nominal cooling capacity 40 150 kW Nominal heating capacity 40 160 kW 50 Hz For the operation of the control please refer to the Control manual for the AR05 017 160 series Installation operati...

Page 2: ...wer supply 14 10 3 Voltage phase imbalance 14 10 4 Recommended wire sections 14 10 5 Field control wiring 15 10 6 Power supply 15 11 WATER CONNECTIONS 15 11 1 Operating precautions and recommendations...

Page 3: ...Refrigerant 26 14 10 High pressure safety switch 26 14 11 Receiver 26 14 12 Four way valve 26 15 OPTIONS AND ACCESSORIES 27 14 13 Control box 27 16 STANDARD MAINTENANCE 28 16 1 Level 1 maintenance 28...

Page 4: ...e declarations of conformity for these products 1 2 Check equipment received Inspect the unit for damage or missing parts If damage is detected or if shipment is incomplete immediately le a claim with...

Page 5: ...hat ensures that people and property are not exposed to refrigerant leaks These uids may be di used in the air but far away from any building air intake or they must be discharged in a quantity that i...

Page 6: ...that has leaked is generally lower than its original calibration The new calibration may a ect the operating range To avoid nuisance trippingorleaks replaceorre calibratethevalve OPERATING CHECKS IMPO...

Page 7: ...is running Be sure pressure is at 0 kPa before removing components or opening a circuit Do not attempt to repair or recondition any safety devices when corrosion or build up of foreign material rust d...

Page 8: ...refer to the chapter Dimensions and clearances to con rm that there is adequate space for all connections and serviceoperations Forthecentreofgravitycoordinates the position of the unit mounting holes...

Page 9: ...the location of xing points weight distribution and coordinates of the centre of gravity refer to the certi ed dimensional drawings B In multiple unit installations maximum four units the side clearan...

Page 10: ...of the centre of gravity refer to the certi ed dimensional drawings B In multiple unit installations maximum four units the side clearance between the units should be increased from 1000 to 2000 mm C...

Page 11: ...hown is a guideline only To nd out the unit refrigerant charge please refer to the unit nameplate In accordance with ISO 9614 1 for information only The values have been rounded and are for informatio...

Page 12: ...onsidered always contact your local Danfoss representative The required protection level for this class is IP43BW according to reference document IEC 60529 All AR05 units are protected to IP44CW and f...

Page 13: ...o add a storage tank to the circuit This tank should be equipped with ba es to allow mixing of the uid water or brine Please refer to the examples below 9 2 Operating range standard units heating mode...

Page 14: ...Pure water litres 600 400 200 1680 1120 560 10 ethylene glycol l 450 300 150 1260 840 420 20 ethylene glycol l 330 220 110 930 620 310 30 ethylene glycol l 270 180 90 750 500 250 40 ethylene glycol l...

Page 15: ...replaced more frequently every 15000 operating hours instead of 25000 hours for an appliacation using water Recommendations on heat exchange uids No NH4 ammonium ions in the water they are very detrim...

Page 16: ...hanger and internal piping that have an automatic supply and by pump cycling units with hydronic module and Reinforced frost protection option Never switch o the water heat exchanger and hydronic circ...

Page 17: ...t leaving pressure information see installation manual Check valve Note x 2 for a dual pump not provided for a single pump Plate heat exchanger Water heat exchanger frost protection heater Installatio...

Page 18: ...et and outlet item 19 As the total system pressure drop is not known exactly at the start up the water ow rate must be adjusted with the control valve to obtain the speci c ow rate for this system Hyd...

Page 19: ...e connected to the unit inlet and outlet item 19 Let the pump run for two consecutive hours to clean the hydronic circuit of the system presence of solid contaminants Take another reading Compare this...

Page 20: ...er is not contaminated Pressure di erential set point control procedure Once the circuit has been cleaned select the hydronic circuit con guration for which the unit selection has been made in general...

Page 21: ...rate that the maximum value or a higher frequency than the maximum value the system settles at the maximum ow rate or maximum frequency and this results in a higher delta T value than the set point H...

Page 22: ...05 120 160 Pressure drop kPa Pressure drop kPa Water ow rate l s Water ow rate l s Water ow rate l s Water ow rate l s Legend 1 AR05 039 2 AR05 045 3 AR05 050 4 AR05 060 5 AR05 070 6 AR05 078 Legend 1...

Page 23: ...AR05 039 2 AR05 045 3 AR05 050 4 AR05 060 5 AR05 070 6 AR05 078 Legend 1 AR05 080 2 AR05 090 3 AR05 100 4 AR05 120 5 AR05 140 Legend 1 AR05 039 2 AR05 045 3 AR05 050 4 AR05 060 5 AR05 070 6 AR05 078...

Page 24: ...peration of two units in master slave mode The control of a master slave assembly is in the entering water and does not require any additional sensors standard con guration It can also be located in t...

Page 25: ...capacity of the heat pump at 7 C outdoor air temperature This requires only a 400 V 3 ph 50 Hz power supply source as well as a connection to the unit via a communication bus For the required con gura...

Page 26: ...densables in the system The presence of moisture changes the colour of the indicator paper in the sight glass 14 7 Filter drier This is a one piece brazed lter drier located in the liquid line The rol...

Page 27: ...complies with JBus protocol Easy connection by communication bus to a building management system AR05 039 160 Bacnet gateway 148C Two directional communications board complies with Bacnet protocol Eas...

Page 28: ...hly or annually depending on the veri cation type In these conditions the following maintenance operations are recommended Carry out all level 1 operations then Electrical checks At least once a year...

Page 29: ...Contactor LC1D12B7 KM 1 7 Contactor LC1D18B7 1 7 Contactor LC1D25B7 2 5 Tunnel terminal screw compressor circuit breaker Circuit breaker 25507 QM 3 6 Circuit breaker 25508 Circuit breaker 25509 Tunne...

Page 30: ...perations 16 7 Water heat exchanger maintenance Check that the insulating foam is intact and securely in place the cooler heaters are operating secure and correctly positioned the water side connectio...

Page 31: ...nt check Is there any shipping damage If so where Will this damage prevent unit start up Unit is level in its installation Power supply agrees with the unit name plate Electrical circuit wiring has be...

Page 32: ...nal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protection included if required litres of Water piping includes...

Page 33: ...t in the LOCAL ON position Unit starts and operates properly Temperatures and pressures WARNING Once the machine has been operating for a while and the temperatures and pressures have stabilized recor...

Page 34: ...34 Installation operation and maintenance instructions VMGFE102 VMGFE102...

Reviews: