background image

28

Installation, operation and maintenance instructions - VMGFE102

16   STANDARD MAINTENANCE

Air conditioning equipment must be maintained by profes-
sional technicians, whilst routine checks can be carried out 
locally by specialised technicians.

All refrigerant charging, removal and draining operations 
must be carried out by a qualifi ed technician and with the 
correct material for the unit. Any inappropriate handling can 
lead to uncontrolled fl uid or pressure leaks.  

WARNING: Before doing any work on the machine ensure that 
the power is switched off . If a refrigerant circuit is opened, it 
must be evacuated, recharged and tested for leaks. Before 
any operation on a refrigerant circuit, it is necessary to 
remove the complete refrigerant charge from the unit with a 
refrigerant charge recovery group.

Simple preventive maintenance will allow you to get the 
best performance from your HVAC unit:

• 

improved cooling performance

• 

reduced power consumption

• 

prevention of accidental component failure

• 

prevention of major time-consuming and costly 
interventions

• 

protection of the environment

There are fi ve maintenance levels for HVAC units, as defi ned 
by the AFNOR X60-010 standard.

16.1 - Level 1 maintenance

See note on page 38

Simple procedures, can be carried out 

by the user on a weekly basis:
• 

Visual inspection for oil traces (sign of a refrigerant leak),

• 

Air heat exchanger (condenser) cleaning - see chapter 
‘Air heat exchanger - level 1’,

• 

Check for removed protection devices, and badly closed 
doors/covers,

• 

Check the unit alarm report when the unit does not work 
(see report in the AR05 017-160 control manual),

• 

General visual inspection for any signs of deterioration,

• 

Verify the charge in the sight-glass,

• 

Check that the water temperature diff erence between 
the heat exchanger inlet and outlet is correct.

16.2 - Level 2 maintenance

This level requires specifi c know-how in the electrical, 
hydronic and mechanical fi elds. It is possible that these skills 
are available locally: existence of a maintenance service, 
industrial site, specialised subcontractor.

The frequency of this maintenance level can be monthly or 
annually depending on the verifi cation type.

In these conditions, the following maintenance operations 
are recommended.

Carry out all level 1 operations, then:

Electrical checks

• 

At least once a year tighten the power circuit electrical 
connections (see table with tightening torques).

• 

Check and retighten all control/command connections, if 
required (see table with tightening torques).

• 

Remove the dust and clean the interior of the control 
boxes, if required.

• 

Check the status of the contactors, disconnect switches 
and capacitors.

• 

Check the presence and the condition of the electrical 
protection devices.

• 

Check the correct operation of all heaters.

• 

Check that no water has penetrated into the control box.

Mechanical checks

• 

Check the tightening of the fan tower, fan, compressor 
and control box fi xing bolts.

Water circuit checks

• 

Check the water connections.

• 

Check the expansion tank for signs of excessive corro-
sion or gas pressure loss and replace it, if necessary.

• 

Purge the water circuit (see chapter ‘Water fl ow control 
procedure’).

• 

Clean the water fi lter (see chapter ‘Water fl ow control 
procedure’).

• 

Replace the pump fi ttings after 15000 hours of operation 
with defrost solution or  after 25000 hours of opera-tion 
with water.

• 

Check the operation of the low water fl ow rate safety 
device.

• 

Check the status of the thermal piping insulation.

• 

Check the concentration of the anti-freeze protection 
solution (ethylene glycol or polyethylene glycol).

Refrigerant circuit

• 

Fully clean the air heat exchangers with a low-pressure jet 
and a bio-degradable cleaner (counter-current cleaning 
- see chapter ‘Air heat exchanger - level 2).

• 

Check the unit operating parameters and compare them 
with previous values.

• 

Carry out an oil contamination test. Replace the oil, if 
necessary.

• 

Check and if necessary re-tighten the Rotalock 
connections in the oil balancing line to the specifi ed 
torque value.

• 

Check the operation of the high-pressure switches. 
Replace them if there is a fault.

• 

Check the fouling of the fi lter drier. Replace it if 
necessary.

• 

Keep and maintain a maintenance sheet, attached to 
each HVAC unit.

All these operations require strict observation of adequate 
safety measures: individual protection garments, compliance 
with all industry regulations, compliance with applicable 
local regulations and using common sense.

Summary of Contents for AR05 017 Series

Page 1: ...t Pumps Nominal cooling capacity 40 150 kW Nominal heating capacity 40 160 kW 50 Hz For the operation of the control please refer to the Control manual for the AR05 017 160 series Installation operati...

Page 2: ...wer supply 14 10 3 Voltage phase imbalance 14 10 4 Recommended wire sections 14 10 5 Field control wiring 15 10 6 Power supply 15 11 WATER CONNECTIONS 15 11 1 Operating precautions and recommendations...

Page 3: ...Refrigerant 26 14 10 High pressure safety switch 26 14 11 Receiver 26 14 12 Four way valve 26 15 OPTIONS AND ACCESSORIES 27 14 13 Control box 27 16 STANDARD MAINTENANCE 28 16 1 Level 1 maintenance 28...

Page 4: ...e declarations of conformity for these products 1 2 Check equipment received Inspect the unit for damage or missing parts If damage is detected or if shipment is incomplete immediately le a claim with...

Page 5: ...hat ensures that people and property are not exposed to refrigerant leaks These uids may be di used in the air but far away from any building air intake or they must be discharged in a quantity that i...

Page 6: ...that has leaked is generally lower than its original calibration The new calibration may a ect the operating range To avoid nuisance trippingorleaks replaceorre calibratethevalve OPERATING CHECKS IMPO...

Page 7: ...is running Be sure pressure is at 0 kPa before removing components or opening a circuit Do not attempt to repair or recondition any safety devices when corrosion or build up of foreign material rust d...

Page 8: ...refer to the chapter Dimensions and clearances to con rm that there is adequate space for all connections and serviceoperations Forthecentreofgravitycoordinates the position of the unit mounting holes...

Page 9: ...the location of xing points weight distribution and coordinates of the centre of gravity refer to the certi ed dimensional drawings B In multiple unit installations maximum four units the side clearan...

Page 10: ...of the centre of gravity refer to the certi ed dimensional drawings B In multiple unit installations maximum four units the side clearance between the units should be increased from 1000 to 2000 mm C...

Page 11: ...hown is a guideline only To nd out the unit refrigerant charge please refer to the unit nameplate In accordance with ISO 9614 1 for information only The values have been rounded and are for informatio...

Page 12: ...onsidered always contact your local Danfoss representative The required protection level for this class is IP43BW according to reference document IEC 60529 All AR05 units are protected to IP44CW and f...

Page 13: ...o add a storage tank to the circuit This tank should be equipped with ba es to allow mixing of the uid water or brine Please refer to the examples below 9 2 Operating range standard units heating mode...

Page 14: ...Pure water litres 600 400 200 1680 1120 560 10 ethylene glycol l 450 300 150 1260 840 420 20 ethylene glycol l 330 220 110 930 620 310 30 ethylene glycol l 270 180 90 750 500 250 40 ethylene glycol l...

Page 15: ...replaced more frequently every 15000 operating hours instead of 25000 hours for an appliacation using water Recommendations on heat exchange uids No NH4 ammonium ions in the water they are very detrim...

Page 16: ...hanger and internal piping that have an automatic supply and by pump cycling units with hydronic module and Reinforced frost protection option Never switch o the water heat exchanger and hydronic circ...

Page 17: ...t leaving pressure information see installation manual Check valve Note x 2 for a dual pump not provided for a single pump Plate heat exchanger Water heat exchanger frost protection heater Installatio...

Page 18: ...et and outlet item 19 As the total system pressure drop is not known exactly at the start up the water ow rate must be adjusted with the control valve to obtain the speci c ow rate for this system Hyd...

Page 19: ...e connected to the unit inlet and outlet item 19 Let the pump run for two consecutive hours to clean the hydronic circuit of the system presence of solid contaminants Take another reading Compare this...

Page 20: ...er is not contaminated Pressure di erential set point control procedure Once the circuit has been cleaned select the hydronic circuit con guration for which the unit selection has been made in general...

Page 21: ...rate that the maximum value or a higher frequency than the maximum value the system settles at the maximum ow rate or maximum frequency and this results in a higher delta T value than the set point H...

Page 22: ...05 120 160 Pressure drop kPa Pressure drop kPa Water ow rate l s Water ow rate l s Water ow rate l s Water ow rate l s Legend 1 AR05 039 2 AR05 045 3 AR05 050 4 AR05 060 5 AR05 070 6 AR05 078 Legend 1...

Page 23: ...AR05 039 2 AR05 045 3 AR05 050 4 AR05 060 5 AR05 070 6 AR05 078 Legend 1 AR05 080 2 AR05 090 3 AR05 100 4 AR05 120 5 AR05 140 Legend 1 AR05 039 2 AR05 045 3 AR05 050 4 AR05 060 5 AR05 070 6 AR05 078...

Page 24: ...peration of two units in master slave mode The control of a master slave assembly is in the entering water and does not require any additional sensors standard con guration It can also be located in t...

Page 25: ...capacity of the heat pump at 7 C outdoor air temperature This requires only a 400 V 3 ph 50 Hz power supply source as well as a connection to the unit via a communication bus For the required con gura...

Page 26: ...densables in the system The presence of moisture changes the colour of the indicator paper in the sight glass 14 7 Filter drier This is a one piece brazed lter drier located in the liquid line The rol...

Page 27: ...complies with JBus protocol Easy connection by communication bus to a building management system AR05 039 160 Bacnet gateway 148C Two directional communications board complies with Bacnet protocol Eas...

Page 28: ...hly or annually depending on the veri cation type In these conditions the following maintenance operations are recommended Carry out all level 1 operations then Electrical checks At least once a year...

Page 29: ...Contactor LC1D12B7 KM 1 7 Contactor LC1D18B7 1 7 Contactor LC1D25B7 2 5 Tunnel terminal screw compressor circuit breaker Circuit breaker 25507 QM 3 6 Circuit breaker 25508 Circuit breaker 25509 Tunne...

Page 30: ...perations 16 7 Water heat exchanger maintenance Check that the insulating foam is intact and securely in place the cooler heaters are operating secure and correctly positioned the water side connectio...

Page 31: ...nt check Is there any shipping damage If so where Will this damage prevent unit start up Unit is level in its installation Power supply agrees with the unit name plate Electrical circuit wiring has be...

Page 32: ...nal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protection included if required litres of Water piping includes...

Page 33: ...t in the LOCAL ON position Unit starts and operates properly Temperatures and pressures WARNING Once the machine has been operating for a while and the temperatures and pressures have stabilized recor...

Page 34: ...34 Installation operation and maintenance instructions VMGFE102 VMGFE102...

Reviews: