AME 685

ENGLISH

Safety Notes

To avoid personal injury and damage 

to devices, it is absolutely essential for 

these instructions and safety notes to 

be read carefully and reviewed prior to 

assembly and use.
Do not dismantle actuator with the safety spring 

function! There is risk of injury and death in the 

event of improper handling!
The actuator is heavy. Handle with care to avoid 

injury or product damage.

Wiring

Do not touch anything on the PCB! 

Do not remove the cover before the 

power supply is fully switched off.

 

NOTE:

 Only basic function as SW1 (Fast/Slow) and 

SW2 (INV/DIR) are active when is no power supply 

on terminal SP and AME actuator operated as AMV.

Actuator mounting to valve 

Stem connections 

Electrical connection 

DIP switch setting 

SW1:  FAST/SLOW – Speed selection 

 

-  FAST; 2.7 s/mm 

-  SLOW; 6 s/mm 

SW2:    DIR/INV – Direct or inverse acting 

selector 

 

-  DIR; the actuator is directly reacting to input 

signal 

-  INV; the actuator is inversely reacting to 

input signal 

SW3:  2-10V/0-10V – Input/output 

-  2-10V; the input signal ranges from 2-10 V 

(voltage input) or 4-20 mA (current input)

-  0-10V; the input signal ranges from 0-10 V 

(voltage input) or 0-20 mA (current input) 

Signal range selector sets Y & X signals. 

SW4:    LIN/MDF – Characteristic modification 

function 

-  LIN; linear correlation between Y signal and 

stem position 

-  MDF (Modified); enables modified 

correlation between Y signal and stem 

position. Degree of modification depends on 

setting of potentiometer CM. 

The function enables to change MCV (Motorised 

Control Valve) characteristic (for example linear 

to logarithmic and logarithmic to linear) and 

works with all combinations of DIP switch 

settings. 

SW5:  100 %/95 % – Stroke limitation 

Adjustable stroke limitation of retracted or 

extended actuator stem position.

DIP switch 5 needs to be reset prior to 

procedure (5.2) to 100 % (5.1) and set to 95 % 

(5.3) until the self-stroking procedure has 

concluded (5.4). Retracted icon (5.5) on actuator 

will blink red-yellow when actuator stops at 

max. retracted stem position (5.5) and will 

blink as long as it is not set to a new retracted 

position (5.6) by pressing buttons 

 

 

to set the required position (observe flow on 

flow meter). Press and hold reset button for 5 

seconds (5.7) and then set new extended stem 

position by pressing buttons 

 

Extended icon (5.8) will blink red-yellow as long 

as it is not set to new extended position by 

pressing and holding reset button for 5 seconds.

SW6:  C/P – Output signal mode selector 

 An output signal is present on terminal 4 

when the position of the actuator is equal 

to or lower than the S4 set point. An output 

signal is present on terminal 5 when the 

position of the actuator is equal to or higher 

than the S5 set point.

SW6:  C; provides a constant output signal on 

terminals 4 & 5, regardless of the input 

signal.

SW6:  P; provides a pulse signal through 

parallel or cascade electrical wiring 

input 1 & 3 dependents from the 

controller to output terminals 4 & 5.

SW7:  Smart function selector: 

-  OFF; the actuator does not try to detect 

oscillations in the system

-  ON; the actuator enables special anti-

oscillation algorithm – In case control signal 

Y on certain point oscillates looking from 

time perspective, algorithm starts to lower 

the amplification of the output to the valve. 

Instead of having static characteristics 

actuator changes to dynamic characteristics. 

After the control signal does not oscillate 

anymore, output to the valve slowly returns 

back to static characteristics.

SW8:  Uy/Iy – Input signal type selector: 

-  Uy; input signal Y is set to voltage (V) 

-  Iy; input signal Y is set to current (mA) 

SW9:  Ux/Ix – Output signal type selector: 

-  Ux; output signal X is set to voltage (V)

-  Ix; output signal X is set to current (mA)

 

NOTE:

 Y detection is disabled if SW8 is set to ON 

position and SW3 is set to OFF position.

Functions accessible from cover

RESET button

The actuator has an external RESET button, 

which is located on the top cover of the actuator 

next to the LED indicators. With this button 

you can enable or disable standby mode (press 

once) or self-stroking mode (press and hold for 5 

seconds). See next paragraph for more details.

Final step of electrical connection 

LED signalisation 

Self-stroking mode 

Self-stroking mode begins automatically the 

first time the actuator is powered on. To start 

the self-stroking procedure, 

press and hold the 

RESET button for 5 seconds

 

 until the green 

light starts flashing. End positions of the valve 

are automatically set and the actuator goes into 

stationary mode 

 and starts responding to the 

control signal.

Manual Operation

Mechanical and electrical operation 

must not be used at the same time!

The actuator can be manually positioned when 

in standby mode or when there is no power 

supply (mechanically).

Actuator type

Mechanical 

operation

Electrical 

operation

AME 685

Stand-By mode 

Press the RESET button for 1 second to enter 

standby mode. The actuator stops in the 

current position and stops responding to any 

control signal. A red light remains constantly 

lit. You can now manually operate the 

actuator.

Mechanical manual operation 

The actuator has a knob & crank on the top of 

the housing which enables manual positioning 

of the actuator.

Use Mechanical manual operation 

only when the power is disconnected. 

Mechanical and electrical operation 

are not allowed to be used at the 

same time!

Electrical manual operation 

The actuator has two buttons on the top of the

housing that are used for electrical manual

positioning (up or down), if the actuator is in

Stand-By mode. First press the RESET button

until the actuator goes to Stand-By mode (red

LED is lit). By pressing the button 

 the stem 

will be extended and by pressing the button 

 the stem will be retracted.

Dimensions 

Part Name

Hazardous Substances Table

Lead (Pb)

Mercury (Hg)

Cadmium (Cd)

Hexavalent Chromium (Cr(VI))

Polybrominated biphenyls (PBB)

Polybrominated diphenyl ethers (PBDE)

Housing

X

O

O

O

O

O

Guide insert

X

O

O

O

O

O

Ball bearing

X

O

O

O

O

O

O:  Indicates that this hazardous substance contained in all of the homogeneous material for this part is below the limit requirement in GB/T 26572;
X:  Indicates that this hazardous substance contained in at least one of the homogeneous material for this part is above the limit requirement in GB/T 26572;

Summary of Contents for AME 685

Page 1: ...10 DANSK AME 685 varme danfoss dk Side 11 DEUTSCH AME 685 www danfoss com Seite 12 FRAN AIS AME 685 www danfoss com Page 13 MAGYAR AME 685 www danfoss com 14 oldal POLSKI AME 685 www danfoss pl Stron...

Page 2: ...AQ19558647231501 010202 2 Danfoss 2022 09 AME 685 AUTO 20 22mm HN 10 5 mm 8 2 Nm 1 40 Nm 1 NH10 10x 30 Nm 1 20 30 Nm 1 22 1 5 95 RH no condensing MAINTENANCE FREE...

Page 3: ...M16 M20 2 Danfoss 2022 09 3 AQ19558647231501 010202 AME 685 AUTO 3 5 4 5mm 0 7mm T 10...

Page 4: ...AC DC Power supply 4 5 SP AC 4 5 1 3 SP output max 4A min 3W 1 SP Input 3 SN 0 V Neutral SP 24 230 V AC DC Power supply 4 5 SP AC 4 5 SP SP output max 4A min 3W 1 SP Input 3 GND 0 V Neutral Y 0 2 10 V...

Page 5: ...2 7 sec mm 6 sec mm T sec 2 7 H 6 H H VF3 DN 200 250 300 Danfoss 2022 09 5 AQ19558647231501 010202 AME 685...

Page 6: ...AQ19558647231501 010202 6 Danfoss 2022 09 AME 685 5s RESET Max extended Max retracted Set new retract Max retracted Kv 5s RESET max extended Set new extended Kv 5s RESET...

Page 7: ...Danfoss 2022 09 7 AQ19558647231501 010202 AME 685 V input 1 3 output 4 5 output 4 5 S4 S5...

Page 8: ...d stem Stilstand motor har n et nederste slutposition spindel helt ude Station rer Betrieb Stellantrieb hat untere Endlage erreicht Antriebsstange vollst ndig ausgefahren Mode stationnaire L actionneu...

Page 9: ...AME 685 5s RESET LED Green Flashing 1 s cycle Flashing 1 s cycle Flashing LED Yellow 1s STAND BY ON STAND BY OFF Constantly lit LED Red L H H 1 min 81 AME 685 VF 3 DN 200 300 AUTO DN L H H1 mm 200 60...

Page 10: ...etect oscillations in the system ON the actuator enables special anti oscillation algorithm In case control signal Y on certain point oscillates looking from time perspective algorithm starts to lower...

Page 11: ...ing Green 1 sec Maks tilbagetrukket Max retracted Maks udtrukket Max extended Indstil ny tilbagetrukket Set new retract Indstil ny udtrukket Set new extended SW6 C P funktionsv lger for udgangssignal...

Page 12: ...ellt wird Dr cken Sie dazu f nf Sekunden die Reset Taste Rot Red Gelb Yellow Blinkt 1 s Flashing 1 sec Gr ne LED blinkt 1 s Flashing Green 1 sec Max eingefahren Max retracted Max ausgefahren Max exten...

Page 13: ...te clignotante 1 s Flashing Green 1 sec R traction max Max retracted Extraction max Max extended D finition d une nouvelle r traction Set new retract R glage nouvelle extraction Set new extended SW6 C...

Page 14: ...en villog amikor a szelepmozgat meg ll a maxim lis visszah zott szelepsz r poz ci ban 5 5 s mindaddig villog am g nem ll tj k be egy j visszah zott poz ci ba 5 6 a gombok megnyom s val hogy a k v nt p...

Page 15: ...wnik zostanie przestawiony do nowego po o enia wysuni cia poprzez naci ni cie i przytrzymanie przez 5 sekund przycisku resetowania Czerwona Red ta Yellow Miga 1 s Flashing 1 sec Miga na zielono 1 s Fl...

Page 16: ...buie resetat nainte de procedura 5 2 la 100 5 1 i setat la 95 5 3 p n c nd procedura de autoreglare se ncheie 5 4 Pictograma retras 5 5 de pe servomotor va clipi n ro u galben c nd servomotorul se opr...

Page 17: ...Motordaki geri ekilmi simgesi 5 5 motor maks geri ekilmi mil konumunda 5 5 durdu unda k rm z sar yan p s ner ve gereken konumu ayarlamak i in d melerine basarak yeni geri ekilmi konuma 5 6 ayarlanmad...

Page 18: ...x extended Set new retract Set new extended SW6 C P S4 4 S5 5 SW6 C 4 5 SW6 P 4 5 1 3 Y Y signal SW7 OFF ON OFF Function OFF ON Function ON SW8 Uy Iy Uy Y V ly Y mA SW9 Ux Ix Ux X V ly X mA SW8 ON SW3...

Page 19: ...W2 DIR INV DIR INV SW3 2 10 0 10 2 10 2 10 4 20 0 10 0 10 0 20 Y X SW4 LIN MDF MCV DIP stroke SW5 100 95 DIP5 5 2 100 5 1 95 5 3 5 4 5 5 5 5 5 6 5 5 7 5 8 5 Red Yellow Flashing 1 sec RESET Flashing Gr...

Page 20: ...73691620 AQ19558647231501 010202 20 Danfoss DCS SGDPT SI 2022 09 AME 685 AME 685 AME 685 RESET 1 Constantly lit LED Red AME 685 AME 685 RESET...

Reviews: