Outline of Control
SiE-05C
220
Functions PLUS Series
4. Outline of Control
4.1
Starting Control
4.1.1
Soft Start
Starts inverter type by low operation frequency in order to prevent refrigerant pump down when the
compressor starts for both cooling and heating.
∗
INV : Inverter, STD : Standard
Herein after we indicate
INV for inverter and STD for standard.
<In Case of Cooling
Only System>
INV outdoor unit
Frequency at start
42Hz + OFF
Hot gas bypass
ON
Liquid injection
ON
STD outdoor unit
Hot gas bypass
ON
INV outdoor unit
Frequency at start
42Hz + OFF
Liquid injection
ON
Function unit (BC)
Solenoid valveY5, Y6, Y7
ON
SI-05C.BOOK Page 220 Monday, November 6, 2000 4:13 PM
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html